88
Example using the settings in the delivered condition
10
0
20
30
30
40
50
60
6
00
7
00
8
00
9
00
Set boiler water or flow temperature in °C
Time in h
A
B
C
D
A
Start of operation with standard
room temperature
B
Set boiler water or flow temperature
in accordance with the selected
heating curve
C
Set boiler water or flow temperature
in accordance with coding address
"FA":
50 °C + 20 % = 60 °C
D
Duration of operation with raised set
boiler water or flow temperature in
accordance with coding address
"Fb":
60 min
Remote control DIP switches
The DIP switches are located on the PCB in the top part of the casing.
Function description
Control functions
(cont.)
5692 799 GB
Содержание VITOLADENS 300-W
Страница 5: ...5 Keyword index 104 Index Index cont 5692 799 GB ...
Страница 106: ...106 5692 799 GB ...
Страница 107: ...107 5692 799 GB ...