39
Calling up code 2
Note
Codes that are irrelevant (due to the
heating system equipment level or the
setting of other codes) will not be dis-
played.
Press the following keys:
1.
L
+
G
simultaneously for
approx. 2 s.
2.
d
to confirm.
3.
a
/
b
for the required coding
address; the address
flashes.
4.
d
to confirm; the value
flashes.
5.
a
/
b
for the selected value.
6.
d
to confirm; the display
briefly shows "
accep-
ted
" (for weather-com-
pensated control units);
the address flashes
again.
7.
a
/
b
for the selection of further
addresses.
8.
L
+
G
approx. 1 s simultane-
ously, to terminate cod-
ing 2.
Complete overview
The coding addresses are grouped according to the following
function areas
. The
respective function area is shown on the display.
The areas are scanned in the following sequence with
a
/
b
:
Function area
Coding addresses
System design
00
Boiler/burner
06 to 54
DHW
56 to 73
General
76 to 9F
Heating circuit A1 (heating circuit without
mixer)
A0 to Fb
Heating circuit with mixer M2
A0 to Fb
Codes
Code 2
5692 799 GB