44
Coding in the delivered condition
Possible change
Boiler/burner
52:0
Without flow temperature
sensor for low loss
header
52:1
With flow temperature sen-
sor for low loss header
(automatic setting on rec-
ognition)
54:0
Without solar control unit 54:1
With a Vitosolic 100
54:2
With a Vitosolic 200 (auto-
matic adjustment after rec-
ognition)
DHW
56:0
DHW temperature adjust-
able from 10 to 60 °C
56:1
DHW temperature adjusta-
ble from 10 to above 60 °C
(max. value subject to cod-
ing card)
Observe the maximum per-
missible DHW temperature
58:0
Without auxiliary function
for DHW heating
58:10
to
58:60
Input of a second set DHW
value; adjustable from 10
to 60 °C
59:0
Cylinder heating:
Starting point -2.5 K
Stopping point +2.5 K
59:1
to
59:10
Starting point adjustable
from 1 to 10 K below the set
value
5b:0
DHW cylinder directly
connected to the boiler
5b:1
DHW cylinder connected
downstream of the low loss
header
60:20
During DHW heating, the
boiler water temperature
is max. 20 K higher than
the set DHW temperature
60:5
to
60:25
The difference between the
boiler water temperature
and the set DHW tempera-
ture is adjustable from 5 to
25 K
62:2
Circulation pump with
2 min run-on
62:0
Circulation pump without
run-on
62:1
to
62:15
Run-on time adjustable
from 1 to 15 min
Codes
Code 2
(cont.)
5692 799 GB