Coding in the delivered condition
Possible change
F8:
–
5
For the operation in re-
duced room tempera-
ture mode, the set room
temperature will be
raised (up to the tem-
perature limit set by
coding address F9) to a
value subject to the out-
side temperature, if the
outside temperature
falls below -5 °C.
Observe the setting of
coding address A3.
F8:+10
to
F8:
–
60
Limit for raising the tem-
perature in reduced
mode adjustable from
+10 to -60 °C
F8:
–
61
Function disabled
F9:
–
14
Below an outside tem-
perature of -14 °C, the
set room temperature
will be raised to the
value selected as set
room temperature, if the
system operates with
the standard room tem-
perature.
F9:+10
to
F9:
–
60
Limit for raising the set
room temperature to the
value selected for stan-
dard mode adjustable
from +10 to -60 °C
FA:20
Raising the set flow
temperature for the
transition from reduced
temperature to standard
room temperature mode
= 20%
FA:0
to
FA:50
Raising the set flow tem-
perature for the transition
from reduced room tem-
perature mode to stan-
dard room temperature
mode, adjustable from 0
to 50%
Fb:30
Duration for raising the
set flow temperature
(see coding address
FA): 60 min
Fb:0
to
Fb:150
Duration for raising the
set flow temperature ad-
justable from 0 to 150
(corresponds to 0 to 300
min)
Code 2
(cont.)
60
Coding
5692
569
GB
Содержание Vitodens 300
Страница 107: ...A1 Main PCB A2 Power supply unit Connection and wiring diagrams external connections 107 Designs 5692 569 GB...
Страница 111: ...Parts lists cont 111 Parts lists 5692 569 GB...
Страница 112: ...Parts lists cont 112 Parts lists 5692 569 GB...
Страница 113: ...Parts lists cont 113 Parts lists 5692 569 GB...
Страница 114: ...Parts lists cont 114 Parts lists 5692 569 GB...
Страница 115: ...Parts lists cont 115 Parts lists 5692 569 GB...
Страница 127: ...127 5692 569 GB...