Coding in the delivered condition
Possible change
Domestic hot water
56:0
DHW temperature ad-
justable from 10 to
60 °C
56:1
Set DHW temperature
adjustable from 10 to
above 60 °C.
Observe the max. per-
missible DHW tempera-
ture
58:0
Without auxiliary func-
tion for DHW heating
58:10
to
58:60
Input of a second set
DHW value; adjustable
from 10 to 60 °C
59:0
Cylinder heating:
Starting point -2.5 K
Stopping point +2.5 K
59:1
to
59:10
Starting point adjustable
from 1-10 K below the set
value
5b:0
DHW cylinder directly
connected to the boiler
5b:1
DHW cylinder connected
downstream of the low
loss header
60:20
*
1
During DHW heating,
the boiler water tem-
perature is max. 20 K
higher than set DHW
temperature
60:5
to
60:25
The difference between
the boiler water tempera-
ture and the set DHW
temperature is adjustable
from 5 to 25 K
62:2
Circulation pump with
2 min run-on time after
cylinder heating
62:0
Circulation pump without
run-on
62:1
to
62:15
Run-on time adjustable
from 1 to 15 min
63:0
*
2
Without auxiliary
function for DHW heat-
ing
63:1
Auxiliary functions: 1 x
daily
63:2
to
63:14
Every 2 days to every 14
days
63:15
2 x daily
65:...
Information regarding
the type of diverter
valve (not adjustable)
65:0
Without diverter valve
65:1
Diverter valve by
Viessmann
65:2
Diverter valve by Wilo
65:3
Diverter valve by Grund-
fos
Code 2
(cont.)
48
Coding
5692
569
GB
*1
Only for weather-compensated control units.
*2
Only for constant temperature control units.
Содержание Vitodens 300
Страница 107: ...A1 Main PCB A2 Power supply unit Connection and wiring diagrams external connections 107 Designs 5692 569 GB...
Страница 111: ...Parts lists cont 111 Parts lists 5692 569 GB...
Страница 112: ...Parts lists cont 112 Parts lists 5692 569 GB...
Страница 113: ...Parts lists cont 113 Parts lists 5692 569 GB...
Страница 114: ...Parts lists cont 114 Parts lists 5692 569 GB...
Страница 115: ...Parts lists cont 115 Parts lists 5692 569 GB...
Страница 127: ...127 5692 569 GB...