Troubleshooting
58
Diagnostics
(continued)
Fault codes
(continued)
Fault code on display
System behavior
*1
Cause
Corrective action
E8
Burner in fault mode
The ionization current lies
outside the permissible range
Check the ionization electrode and
cable. Press ”
RESET”.
E9
Burner in fault mode
The ionization current lies
outside the permissible range
during calibration
Check the ionization electrode and
cable. Check venting system for
leaks. Press ”
RESET”.
EA
Burner in fault mode
The ionization current lies
outside the permissible range
during calibration
Check the ionization electrode and
cable.
Press ”
RESET”.
Eb
Burner blocked
Boiler control initiated a
combustion
calibration but could not
complete the
process
- Heat generated by boiler must be
removed (boiler is cycling on
temperature limits, before calibration
process is complete)
- Check the connecting cable and the
ionization electrode, check the flue
gas system (flue gas recirculation).
- Verify pump operation
- Switching points of flow switch
marginal (not enough flow)
- Check coding card
- Check gas valve
- Check coding address 82
- Also see address 12:__
Press ”
RESET”.
EE
Burner in fault mode
At burner start, flame signal
is missing or too weak
Check the ionization electrode and
cable.
Check gas supply, condensate drain,
ignition and ignition module
Press ”
RESET”.
EF
Burner in fault mode
Flame is lost immediately
after it has built (during the
safety time)
Check gas supply, check flue gas/
exhaust pipe/air intake for flue gas
recirculation, check ionization
electrode (replace if necessary)
Press ”
RESET”.
EC
Burner in fault mode
The ionization current lies
outside the permissible range
during calibration
Check the ionization electrode and
cable. Press ”
RESET”.
Ed
Burner in fault mode
Internal fault
Replace the control unit.
F0
Burner blocked
Internal fault
Replace the control unit.
F1
Burner in fault mode
Maximum flue gas
temperature exceeded
(230ºF / 110ºC).
Check heating system fill
level. Bleed air from system.
Press ”
RESET” after vent system
has cooled down.
5