Coding
45
Coding Level 2
(continued)
Overview of coding addresses
(continued)
Coding (factory default setting)
Possible change
General
7F:1
Detached house
7F:0
Apartment
Separate adjustment of holiday program and
time program for DHW heating, as option
80:1
A fault message is displayed, providing a
fault is active for at least 5 sec.
80:0
Immediate fault message
80:1
A fault message is displayed, providing a
fault is active for at least 5 sec.
80:2
to
80:199
The fault message is issued after a delay that
is adjustable from 10 sec. to 995 sec.;
1 increment = 5 sec.
81:1
Automatic daylight savings time change-
over
(daylight savings date in European countries)
81:0
Manual daylight savings time changeover
81:1
Automatic daylight savings time change-
over
(daylight savings date in European countries)
81:3
Accept time via LON communication
82:0
Operation with natural gas
82:1
Operation with LPG (only adjustable if coding
address 11:9 has been set).
85:0
Standard mode
85:1
Manual calibration of the combustion controller
(only adjustable if coding address 11:9 has
been set). The red fault indicator also flashes
during calibration. The process has terminated
when the red fault indicator no longer
flashes (after approx. 1 min.).
Note:
Heat generated by the boiler must be
dispersed during manual calibration.
88:0
Temperature displayed in °C (Celsius)
88:1
Temperature displayed in °F (Fahrenheit)
8A:175
No adjustment
90:128
Time constant for calculating the
adjusted outdoor temperature
21.3 hours
90:0
to
90:199
Fast (low values) or slow (high values)
matching of the supply temperature,
subject to the setpoint when the outdoor
temperature changes;
1 increment = 10 min.
91:0
No external heating program changeover
via connection
aVD
in the power/pump
module (see page 64 in this manual)
91:1
The external heating program changeover
affects the htg. circuit without mixing A1
via connection
in the power/pump
module (see page 64 in this manual)
91:2
The external heating program changeover
affects the htg. circuit with mixing M2
91:3
The external heating program changeover
affects the htg. circuit without mixing valve A1
and the htg. circuit with mixing valve M2
97:0
With LON communication module: The
outdoor temperature of the sensor
connected to the control unit is utilized
internally
97:1
The control unit receives the outdoor
temperature
internally
97:2
Control unit transmits the outdoor temperature
9b:70
Minimum boiler water temperature
setpoint in case of external demand
9b:1
to
9b:127
Minimum boiler water setpoint temperature
adjustable from 34 to 261°F / 1 to 127°C
(limited by the boiler coding card)
9C:20
Monitoring LON participants
When there is no response from a
participant, values defaulted by the control
9C:0
No monitoring
participant, values defaulted by the control
unit are used after 20 min. and a fault
message is issued
9C:0
Time adjustable from 5 to 60 min.
5
4
4
3
2
0
7
v
1
.5