Set-up and Connections
7
Tank Set-up
(continued)
Provide sufficient clearances towards
the wall to allow the aquastat to be
operated (if installed).
Recommended installation clearances for service access
Rear
inches
mm
18
460
Sides
May be reduced if rear pipe connections can be reached with less clearance
inches
mm
12
300
Top
inches
mm
12
300
Front
inches
mm
26
650
Minimum clearances to combustibles
All sides
inches
mm
0
0
5285
658
v2
.1
Install the DHW tank in a frost-
protected and draft-free room.
Otherwise it must be drained when
not in use, in order to reduce the risk
of damages caused by freezing.
CAUTION
IMPORTANT
26” / 650 mm
Fig. 2