64
5.
!
Please note
To prevent equipment dam-
age, check the flow and return
connections of the heat pump
secondary circuit for
leaks
.
In the case of leaks, drain off
water via drain valve
B
.
Check the seating of seal
rings.
Always
replace dis-
lodged seal rings.
6.
Close the on-site BDF valve.
7.
To prevent damage to electrical com-
ponents, connect an on-site hose to
manual air vent valve
A
. Open man-
ual air vent valve.
8.
Close manual air vent valve
A
after
venting has been completed.
9.
Check system pressure. Top up with
water if required.
Checking the expansion vessel and heating circuit pressure
Carry out this test on a cold system.
Note
Only use anti-corrosion agents that have
been approved for heat pumps with
DHW heating via single-walled heat
exchangers (DHW cylinders).
1.
If an on-site shut-off valve is installed,
close it.
Otherwise drain the heating system
on the heating water side until the
pressure gauge indicates "0".
2.
If the pre-charge pressure of the
expansion vessel is lower than the
static system pressure, top up with
sufficient nitrogen to raise the pre-
charge pressure of the expansion
vessel by 0.1 to 0.2 bar (10 to
20 kPa) higher than the static system
pressure.
Example:
Static head (distance between the
heat source and the highest heating
surface) 10 m
Equivalent to a static pressure of
1 bar (0.1 MPa).
3.
Top up with water until the filling pres-
sure exceeds the pre-charge pres-
sure of the expansion vessel.
On a cold system, the charge pres-
sure must be approx. 0.2 bar
(20 kPa) higher than the static pres-
sure.
4.
During commissioning, mark this
value on the pressure gauge as min-
imum charge pressure.
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)
5516 436 GB
Содержание VITOCAL 300-A
Страница 5: ...5 Certificates Declaration of conformity 116 Keyword index 117 Index Index cont 5516 436 GB ...
Страница 79: ...79 8x Troubleshooting Repairs cont 5516 436 GB Service ...
Страница 94: ...94 0011 0010 0009 0008 0004 0005 0006 0007 0001 0003 0002 Parts lists Additional components cont 5516 436 GB ...
Страница 96: ...96 0007 0007 0007 0004 0005 0004 0003 0003 0003 0003 0006 0002 0001 Parts lists Air module cont 5516 436 GB ...
Страница 122: ...122 5516 436 GB ...
Страница 123: ...123 5516 436 GB ...