19
Connect heating circuits and DHW cylinder in the building
1.
Equip the secondary circuit on site
with an expansion vessel and safety
assembly (in accordance with
EN 12828).
Fit the safety assembly to the on-site
line in the heating water return.
2.
Connect secondary lines to the lines
of the hydraulic connection set
(accessory).
!
Please note
To prevent appliance dam-
age,
connect on-site secondary
lines so that they are free of
load and torque stresses.
Make tight hydraulic connec-
tions on the secondary side.
3.
Fill and vent secondary circuit.
4.
Thermally insulate pipes inside the
building.
5.
Connect the drain hose to the safety
valve.
Connect the drain hose to the public
sewage system with a fall and a pipe
vent.
Note
■ In underfloor heating circuits, install a
temperature limiter to restrict the max-
imum temperature of underfloor heat-
ing systems.
■ Safeguard the minimum flow rate: see
"Specification".
Fitting the flow temperature sensor, secondary circuit
The flow temperature sensor for the sec-
ondary circuit is installed in the heating
water flow
inside the building
.
Note
If an instantaneous heating water heater
is installed, fit the flow temperature sen-
sor for the secondary circuit in the heat-
ing water flow downstream of the
instantaneous heating water heater.
Installation sequence
Making the hydraulic connections
(cont.)
5516 436 GB
Installation
Содержание VITOCAL 300-A
Страница 5: ...5 Certificates Declaration of conformity 116 Keyword index 117 Index Index cont 5516 436 GB ...
Страница 79: ...79 8x Troubleshooting Repairs cont 5516 436 GB Service ...
Страница 94: ...94 0011 0010 0009 0008 0004 0005 0006 0007 0001 0003 0002 Parts lists Additional components cont 5516 436 GB ...
Страница 96: ...96 0007 0007 0007 0004 0005 0004 0003 0003 0003 0003 0006 0002 0001 Parts lists Air module cont 5516 436 GB ...
Страница 122: ...122 5516 436 GB ...
Страница 123: ...123 5516 436 GB ...