Technical Data
4
VITOROND 200, VD2A
Technical Data
Boiler model
VD2A-
125
160
195
230
270
Input (oil)
*
1
MBH
490
628
765
902
1059
kW
144
184
224
264
310
Input (gas)
*
1
MBH
508
650
792
934
1096
kW
149
190
232
274
321
Output (oil/gas)
*
2
MBH
433
553
672
794
932
kW
127
162
197
232
272
Combustion efficiency (oil)
%
87.7
87.3
87.3
87.3
87.3
Combustion efficiency (gas)
%
84.7
84.8
84.8
84.8
84.8
Thermal efficiency (oil)
%
87.9
87.6
87.4
87.3
87.2
Thermal efficiency (gas)
%
85.2
85.1
84.8
84.8
84.7
Number of cast iron sections
4
5
6
7
8
Cast iron block dimensions
*
3
Length (dimension f)
Width (dimension c)
Height (dimension b)
in
mm
in
mm
in
mm
26½
670
31
790
35
884
33
840
31
790
35
884
39¾
1010
31
790
35
884
46½
1180
31
790
35
884
53¼
1350
31
790
35
884
Cast iron section dimensions
*
3
Front section (with combustion
chamber door)(dimension j)
Intermediate section
(dimension i)
Rear section (with flue gas
collar)
in
mm
in
mm
in
mm
35 x 31 x 11½
885 x 790 x 290
34 x 26¾ x 6¾
860 x 680 x 170
35 x 34 x 10½
885 x 860 x 270
Dimensions (with insul.
jacket)
*
3
Total length (dimension g)
Total width with side-
mounted Vitotronic NR2
control (dimension e)
Total width (dimension d)
Total height with boiler base
(dimension h)
Total height with supply
header (dimension a)
in
mm
in
mm
in
mm
in
mm
in
mm
35¾
905
40½
1030
34
860
39½
1007
58½
1485
42¼
1075
40½
1030
34
860
39½
1007
58½
1485
49
1240
40½
1030
34
860
39½
1007
58½
1485
55½
1410
40½
1030
34
860
39½
1007
58½
1485
62¼
1580
40½
1030
34
860
39½
1007
58½
1485
Weight
Front section (with combustion
chamber door)
Intermediate section
Rear section (with flue gas
collar)
Cast iron heat exchanger block
Overall weight
(complete with jacket,
without burner)
lbs
kg
lbs
kg
lbs
kg
lbs
kg
lbs
kg
352
160
220
100
242
110
1122
510
1201
545
352
160
220
100
242
110
1353
615
1441
655
352
160
220
100
242
110
1584
720
1675
760
352
160
220
100
242
110
1760
800
1874
850
352
160
220
100
242
110
1991
905
2127
965
*1
Input ratings are based on ANSI Z21.13a*CSA 4.9a-2007 - Gas Fired Steam and Hot Water Boilers;
CSA B140.7-05 - Oil Burning Equipment - Steam and Hot Water Boilers;
CSA B140.0-03 - Oil Burning Equipment - General Requirements;
UL 726 - 7th ed. - Oil-Fired Boiler Assemblies;
and UL 795 - Commercial Industrial Gas Heating Equipment.
*
2
Output ratings are based on the IBR BTS-2000 “method to determine efficiency of commercial space heating boilers”.
*3
Inch dimensions are rounded to the nearest ¼”.
5
3
5
4
7
8
7
v
1
.2