System Design Considerations
VITOROND 200, VD2
13
System Design Considerations
Burner calibration
With 2-stage and fully modulating burners,
ensure that the chimney is compatible with
the lower flue gas temperatures associated
with partial load conditions set on the
burner.
2-Stage burner
When used with the Dekamatik or Vitotronic
control, the following minimum heating
outputs are applicable to protect the boiler:
- 60% of outputs stated in the Technical
Data table on page 4.
Fully modulating burner
The minimum boiler water temperature is:
– 140°F / 60°C with oil,
– 149°F / 65°C with natural gas.
Set the return temperature elevation system
to maintain a minimum value of 127°F /
53°C.
Venting
The Vitorond 200, VD2 boiler is approved
as a
Category I
appliance and must be
vented accordingly.
Chimney
For proper operation of the Vitorond 200,
VD2 boiler, all products of combustion must
be safely vented to the outdoors, while
ensuring that flue gases do not cool
prematurely.
It is critical that the chimney system be
properly designed to handle the relatively
cool flue gas temperatures produced by the
Vitorond 200, VD2 boiler.
If the chimney system lacks sufficient
insulation and/or the chimney diameter is
too large, corrosive and damaging
condensation will result due to flue gases
cooling too quickly. If a calculated chimney
diameter lies between two values, the larger
diameter should be selected.
Chimney
(continued)
The chimney connection length between the
boiler vent pipe collar and the chimney must
be installed with insulation.
Vent pipe collar diameter does not
automatically indicate vent/chimney size.
We recommend consulting a reputable
chimney installer for advice in
project-specific circumstances.
When installing the Vitorond 200, VD2
boiler, it is necessary to install a barometric
draft regulator in the chimney/vent for
proper operation of the boiler.
Install the barometric draft regulator within
5 to 7 ft. / 1½ to 2 m from the breeching
outlet located at the rear of the boiler.
Barometric draft regulator type
For natural gas or propane applications, use
a double-acting type.
For #2 fuel oil applications, use a
single-acting type.
Barometric draft regulator diameter
The barometric draft regulator
must be the
same diameter
opening as the chimney for
which the vent is sized.
For example, a 14” chimney would require a
14” barometric draft regulator. Do
not
size
the barometric draft regulator to the
breeching outlet of the boiler, unless the
chimney is also intended to be of that
diameter.
The size of the flue gas outlet on the boiler
does not automatically determine the
horizontal breeching, or the actual chimney
diameter. The chimney size must be
designed for the actual boiler model and its
input.
Combustion air supply
The boiler must not be located in areas or
rooms where chemicals containing chlorine,
bromine, fluorine, or other corrosive
chemicals are stored. Examples include
refrigerants, bleach, paint, paint thinner, hair
spray, cleaning solvents, water softener
salt, etc. The combustion air must not be
contaminated with any amount of the above
mentioned chemicals.
Boiler should never be installed in areas
where excessive dust, high humidity, or risk
of frost exist. Ensure adequate ventilation
and supply of fresh combustion air.
Consult Viessmann with uncertainties in
regard to a suitable boiler installation
location.
This boiler/burner unit needs clean fresh air
for safe operation. Provisions for
combustion and ventilation air must be
made at time of installation. For oil-fired
boilers, use the “Installation Code for Oil
Burning Equipment CAN/CSA-B139”
(Canada), or NFPA 31 (USA). For gas or
propane installations, use the “Natural Gas
Installation Code CAN/CSA-B149.1 or
B149.2” (Canada), or “National Fuel Gas
Code ANSI Z223.1” (USA), and/or
provisions of local codes.
The sizing methods outlined in the above
codes should be used when installing a
round duct to supply combustion air from
the outside.
Warranty
Our warranty does not cover damages
resulting from the following:
–
Corrosion caused by flue gas condensation
due to low boiler water and/or return
water temperatures.
–
Operation with contaminated fill and
supplementary feed water.
System layout
The boiler water temperature limit is factory
set to 167°F / 75°C.
The boiler water temperature limit can be
increased by altering the adjustable high
limit to increase the supply water
temperature.
To minimize piping losses of the system,
however, Viessmann recommends that the
radiation and domestic hot water production
in the system be designed for a 158°F /
70°C boiler supply water temperature.
5285
661
v1
.4
The Vitorond 200, VD2 boiler is not
approved for side wall venting.
CAUTION
IMPORTANT
Barometric draft regulator