PYROMAT-DYN 

 

 

 

 

Köb Holzheizsysteme GmbH, Flotzbachstr. 33,  A-6922 Wolfurt, Tel. +43/5574/6770-0, Fax 65707, E-Mail: [email protected] 

Subject to technical changes 

3010-1

2009-03-01_GB

Description: 
 

The PYROMAT-DYN is a boiler with patented double combustion chamber. Which means that the burner system enables 
optimized operation with automatic loading (shavings, chippings from waste wood, wood chippings, max. W35; G50) and 
may also be used with logs. A large loading shaft with loading lid and separate grid has been fitted in front of the main 
combustion chamber to make loading wood easy. In automatic operation, the burner system is suitable for all dry to moist 
wood fuels (max. W35). The control is integrated into the burner system with connector-ready cabling to the sensors and 
motors. Which permits simple and rapid installation. The PYROMAT-DYN has been tested and approved in accordance 
with the latest quality criteria in compliance with EN 303-5 heating boilers for solid fuels,  
CE certification as per European Machinery Directive and continuous quality assurance by TÜV. 
 
Max. flow temperature:  

100°C 

Max. operating pressure: 

3.0 bar 

Electric connection: 

3 x 400V 

Safety heat exchanger: 

Built into the boiler 

 
Function: 

In manual operation, chopped wood and waste wood are degassed on the incineration grate situated before the  

 

main combustion chamber. Simultaneous operation with automatic loading is not possible. 

-     In automatic operation the feed auger conveys the material to be burned into the main combustion chamber for 

degasification.  

 

The fasteners for the burn-back sensor and the thermally operated extinguisher valve are situated on the conveyor 
pipe.  Above the auger, there is a metering container with a light barrier to ascertain the level of the fuel isolating layer 
required according to TRD 414.  

In automatic operation the material to be incinerated is ignited automatically by an electric hot air blower. 

 

The combustion gases are entirely burned out in the afterburn chamber together with secondary airflow. 

The ash is mechanically removed from the main combustion chamber. 

In the upright pipe heat exchanger, the thermal energy from the combustion gases is transferred to  

 

the boiler water. The vertical surfaces of the heat exchanger are regularly cleaned by motor-driven,  

 

moving coil springs.  

The speed-controlled exhaust blower was specially designed for operation in wood heating systems and is very quiet.  

The negative pressure created by it produces a high degree of safety against burn-back in automatic operation and a 
convenient feed function in manual operation. 

An integrated heat management system (accumulator-temperature-guided with return circuit valve) enables the best 
possible controlled operation. 

 

Scope of delivery: 

-

 

Boiler with double combustion chamber, ash pan, kindling and cleaning utensils, coil springs for the heat exchanger 
cleaning system, mechanical drive with position sensor for removing the ash from the main combustion chamber.  

Exhaust blower, plug-and-play  

Integrated  ECOTRONIC control system (decentralised microprocessor system via CAN-bus), consisting of:  

 

Boiler control panel, control module for mounting preferably on a wall, bus cable for the drive motors wired to  

 output 

plug 

Feed auger with isolating layer, incl. Starttec drive via CAN-bus (including data transmission line) for gentle start-up, 
automatic reversing and overload safeguard, light barriers for combustion chamber and metering container 

-

 

Automatic ignition system 

Burner group ready-installed on connecting flange, consisting of burner pump, two blockage units  

 

Burner control valve, forward and return flow sensors incl. fittings.  

-

 

Three KTY heat accumulator sensors, incl. dipping shell (1/2" x 280 mm long) wired together to plug 

-

 

Four-pin master switch, uninstalled (for installation near the control module) 

 
ACCESSORIES for PYROMAT-DYN (Article KPM-…) at extra charge: 
 
Name Article 

Text 

Sizes 

Use 

Reduction exhaust connection   

KPM-… 

3110 

3110 

existing chimney 180 mm dia.  

Exhaust blower-intake port 90° 

KPM-… 

3110 

3110 

special exhaust gas conveyance 

Exhaust gas deduster 

KPM-… 

3110 

3110 

optional 

De-ashing into the container 20 L 

KPM-DYN-AS  3200 

3200 

optional 

ECO function for PYROMAT-DYN 

LSR-DYN 

3200 

   -  

for use with logs; incl. storage 

Error report 230 V 

ECO-ZA 

3200 

   -  

optional 

External requirements 

ECO-ANF 

3200 

   -  

optional 

Discharge systems 

ADE/ADF 

3300 

3300 

material transport silo to boiler 

Heater control, module extensions 

ECO-… 

4000ff     - 

optional 

Data cable for operating module 

ECO-… 

4020 

   -  

required 

Boiler safety devices 

K-… 

4500  

   -  

optional 

Extinguishing equipment 

K-… 

4550 

4550 

optional 

Содержание KOB PYROMAT DYN 45

Страница 1: ...Instructions for Assembly and Installation PYROMAT DYN 45 to DYN 85 5726 786 GB 10 2009 Version 0 1 Please keep safe...

Страница 2: ...by K b Holzheizsysteme GmbH Flotzbachstra e 33 A 6922 Wolfurt All rights reserved including photomechanical re production and storage in electronic media Viessmann Group...

Страница 3: ...Automatically Triggering System for the Material Supply System ATSMS 7 7 2 2 Slide valve type MBA 7 7 2 3 Rotary valve type MBS 7 7 2 4 Double rotary valve with pressure compensation 7 7 3 Fire protec...

Страница 4: ...with European Standard EN 303 5 1999 In addition the PYROMAT DYN meets all European national deviations relating to tightened regulations relevant to emission limits and efficiencies Austria Art 15a...

Страница 5: ...AT DYN is equipped with an exhaust blower and so it is a fireplace not requiring a draft The design of the chimney should be carried out as for a fireplace with an oil or gas blast burner not requirin...

Страница 6: ...on the opposite side feed side Screw the lid tight to the motor and rod assembly and connect the electric line Run the squared shaft end from the de ashing agi tator through the drilled hole in the gr...

Страница 7: ...lid flange Unplug plugs 6 remove servomotor burner con trol valve 4 and unscrew screws on the rear wall 5 Light barrier ember monitoring system receiver EO98VB3S770 Abbreviated designation B 1G 2 Tran...

Страница 8: ...con densation of the exhaust gases the burner tem perature must in no case be less than 70 C For this a burner circuit pump should be provided with a boiler control valve according to the diagram Spec...

Страница 9: ...he fire protection regulations for wood heating systems vary for each specific country The regulations valid for the respective place of installation must be complied with 7 1 Protection for the burne...

Страница 10: ...pproved in non pressurised fuel storage units for all cases and according to TRVB 118 test certificate BV 2979 89 is considered as a suitable back burn safeguarding device 7 2 3 Rotary valve type MBS...

Страница 11: ...ty valve mounted on burner and or burner inlet 4 Thermal run off safety valve connected to the cold water mains 5 The sensor for the thermal run off safety valve is in the dipping shell 6 The containe...

Страница 12: ...ulating valve as per the diagram The burner circuit should be configured such that the temperature difference between the forward and return flow is equal to or less than 15 C This is given in the des...

Страница 13: ...P S 30 7 EM VXG48 40 SQS35 00 NW 50 R 1 NW 32 1 Connecting thread for inlet 2 Length of the exhaust pipe up to 4 0 m for longer lines see DIN 4751 Part 2 c Designation of the motors sensors and safety...

Страница 14: ...a burner circuit pump should be provided with a modulating valve as per the diagram The burner circuit should be configured such that the temperature difference between the forward and return flow is...

Страница 15: ...the motors sensors and safety switches Motors Electrical probes and sensors M1 Exhaust blower B1G 1 Transmitter light barrier for embers opposite slide in module M2 Feed auger B1G 2 Receiver light ba...

Страница 16: ...ted in metal 1 2 with fixed pipework K SLE and K SLV It must not be possible to shut off the cold water inlet without the aid of tools Be especially sure to comply with Point 5 of the Installation Ins...

Страница 17: ...y tap VBF 21 80 80 100 SQL 33 Counter flange seals ZH 3 100 7388165 3 way tap VBF 21 100 100 160 SQL 33 Counter flange seals ZH 3 125 7388053 3 way tap VBF 21 125 125 550 SQL 33 Counter flange seals P...

Страница 18: ...nection LVW 65 Art No LVW 65 V 7387862 Connecting two model LVW 65 manifolds produces a manifold for four to six consumer groups The connection is assembled at the factory to assure an accurate fit He...

Страница 19: ...leakage losses One ball valve with screwed connection for mounting on motor valve VXG 48 25 SSY 319 with pump connection on bottom One ball valve with thermometer socket and screwed connection with pu...

Страница 20: ...is transferred to the boiler water The vertical surfaces of the heat exchanger are regularly cleaned by motor driven moving coil springs The speed controlled exhaust blower was specially designed for...

Страница 21: ...tors refer to spec sheets Category 4 The operation of the heating control units is all carried out in the control module for the burner system Each controller is operated by a separate pushbutton For...

Страница 22: ...nal heat output g s 35 56 68 Average exhaust gas temperature at maximum nominal load C 138 136 134 Average exhaust gas temperature at minimum nominal load C 79 78 77 Maximum water content forest wood...

Страница 23: ...achstr 33 A 6922 Wolfurt Tel 43 5574 6770 0 Fax 65707 E Mail office kob cc Subject to technical changes 3010 4 2009 03 01_GB Dimensional drawing Feed auger available either left or right turning Right...

Страница 24: ...00 100 S Connection for exhaust blower 1 200 200 200 T Width of firebox 550 550 550 U Depth of firebox 300 400 400 W Outlet exhaust blower 293 293 293 Z Slide in module flange 650 765 800 a Connection...

Страница 25: ...r is insulated and cased in powder coated steel plate When operated according to the operating instructions dust emissions even when chips are incinerated are under 150 mg Nm based on 13 residual oxyg...

Страница 26: ...er ECO S1 1 1 2 4050 Controllers for solar systems Solar domestic water heating system ECO S3 1 2 2 4050 Modules and combinations possible see Spec Sheet 4020 Extra charge for control system module Ex...

Страница 27: ...th Extended Keyboard Art No ECO 13 7387820 A control module with an additional row of buttons to operate a maximum of 12 controllers PYROMAT DYN PYROT 13 controllers Pyromat ECO Data transmission line...

Страница 28: ...ol module in the heating room Version 2 Decentral control system module e g in annex building Only one control module possible Visualization with PC for extra cost please refer to Data Sheet 4090 Cont...

Страница 29: ...0 0 Fax 65707 E Mail office kob cc Subject to technical changes 4020 3 2009 03 01_GB Example of how to connect the CAN BUS cables for the PYROT Control system module 1 3 possible Visualization with PC...

Страница 30: ...nto operation the additional heat generator disconnects and the closed shut off valve prevents it from being flowed through The boiler temperature is variably regulated to a minimum temperature accord...

Страница 31: ...troller output for pump 1 mixing valve 2 and burner 3 Note Only for PYROMAT DYN without ECO function and PYROT with hydraulic switcher See Hydraulic Drawing 3950 PYROMAT ECO or 6960 PYROMAT DYN with E...

Страница 32: ...n for annex building Controller output for pump 1 mixing valve 1 and changeover valve 3 Flow sensor QAD 21 uninstalled Domestic water sensor QAZ 21 5220 with dipping shell x 200 mm uninstalled Thermos...

Страница 33: ...rerequisite The heating times day and week program can be adjusted via the integrated timer Scope of delivery Pushbutton for domestic water heater Controller output for pump 1 and shut off valve 2 Dom...

Страница 34: ...rcuit is for heating the heat accumulator at the back bottom and the third circuit is for heating the heat accumulator at the front top The heat accumulator is heated by an externally situated plate h...

Страница 35: ...n series T T T T M II IV 3 I 1 4 2 example 3 accumulators in series I solar collector II solar station with solar pump III thermostatic water mixer IV plate heat exchanger 1 solar pump 2 intlet valve...

Страница 36: ...customer Operating system Windows 98 2000 XP Available hard disk storage space at least 50 MB RAM at least 128 MB RAM Per boiler 1 available serial interface Visualisation Supplementary Function Art...

Страница 37: ...d Draining the heating room and silo room with all the ducts and shafts required for installing the entire facility e Unloading the scope of the delivery from the truck unless the delivery has been ex...

Страница 38: ...of the delivery Due to the great forces that develop this performance should be furnished according to the instructions of an expert architect or structural engineer in accordance with the supplier s...

Страница 39: ...2 Superfines dust wood particles smaller than 1 0 mm as per NORM M 7133 2 1 Without pre dryer max 10 0 of the total mass consequence of substantial overstepping of limit Temperature peaks Slag format...

Страница 40: ...remnants D 40 to 60 mm k1 S 650 less than W10 Pellets conforming to standards untreated D 6 to 10 mm k2 S 650 less than W10 Pellets conforming to standards untreated D 11 to 15 mm 6 Maximum water cont...

Страница 41: ...the technical clarification does not permit production on time for which the supplier is without blame the supplier is excused from the deadline commitment 3 The supplier is entitled to withhold the...

Страница 42: ...t in the fire proof coatings surface wear wear around the edges cracks etc that do not lead to any malfunction of the equipment are not covered by warranty New parts carry the stipulated new parts war...

Страница 43: ...e 73 23 EEC Low Voltage Directive 89 336 EEC EMC Directive 97 23 EC Pressure Equipment Directive Applied standards EN 303 5 DIN 4702 Solid fuel burners manual and automatic feeder systems EN 60335 1 A...

Страница 44: ...K b Holzheizsysteme GmbH Flotzbachstrasse 33 A 6922 Wolfurt Tel 43 55 74 67 70 0 Fax 43 55 74 65 7 07 office kob cc www kob cc Viessmann Group www viessmann com...

Отзывы: