88
Coding in the delivered condition
Possible change
b0:0
With remote control:
Heating mode/reduced
mode: Weather-compen-
sated (only for weather-
compensated control
units; change the code
only for the heating circuit
with mixer)
b0:1
Heating mode: Weather-
compensated
Reduced mode: With room
temperature hook-up
b0:2
Heating mode: With room
temperature hook-up
Reduced mode: Weather-
compensated
b0:3
Heating mode/reduced
mode: With room tempera-
ture hook-up
b2:8
With remote control and
for the heating circuit,
operation with room tem-
perature hook-up must be
programmed: Room influ-
ence factor 8 (only for
weather-compensated
control units; change the
code only for the heating
circuit with mixer)
b2:0
Without room influence
b2:1
to
b2:64
Room influence factor
adjustable from 1 to 64
b5:0
With remote control: No
room temperature-
dependent heating circuit
pump logic function (only
for weather-compensa-
ted control units; change
the code only for the heat-
ing circuit with mixer)
b5:1
to
b5:8
Heating circuit pump logic
function, see the following
table:
Parameter
address b5:...
With heating circuit pump logic function:
Heating circuit pump "OFF"
Heating circuit pump "ON"
1
RT
actual
> RT
set
+ 5 K
RT
actual
< RT
set
+ 4 K
2
RT
actual
> RT
set
+ 4 K
RT
actual
< RT
set
+ 3 K
3
RT
actual
> RT
set
+ 3 K
RT
actual
< RT
set
+ 2 K
4
RT
actual
> RT
set
+ 2 K
RT
actual
< RT
set
+ 1 K
5
RT
actual
> RT
set
+ 1 K
RT
actual
< RT
set
6
RT
actual
> RT
set
RT
actual
< RT
set
- 1 K
7
RT
actual
> RT
set
- 1 K
RT
actual
< RT
set
- 2 K
8
RT
actual
> RT
set
- 2 K
RT
actual
< RT
set
- 3 K
Code 2
Heating circuit 1, heating circuit 2, heating…
(cont.)
5457 552 GB