84
Coding in the delivered condition
Possible change
65:...
Information regarding the
type of diverter valve (not
adjustable):
0: no diverter valve
1: Viessmann diverter
valve
2: Wilo diverter valve
3: Grundfos diverter valve
6C:100
Set speed; internal circu-
lation pump with DHW
heating 100 %
6C:0
to
6C:100
Set speed adjustable from
0 to 100 %
6F:...
Maximum output for
DHW heating in %, speci-
fied by the boiler coding
card
6F:0
to
6F:100
Max. output during DHW
heating adjustable from
min. output to 100 %
71:0
DHW circulation pump:
"ON" in accordance with
the time program (only for
weather-compensated
control units)
71:1
"OFF" during DHW heating
to the first set value
71:2
"ON" during DHW heating
to the first set value
72:0
DHW circulation pump:
"ON" in accordance with
the time program (only for
weather-compensated
control units)
72:1
"OFF" during DHW heating
to the second set value
72:2
"ON" during DHW heating
to the second set value
73:0
DHW circulation pump:
"ON" in accordance with
the time program (only for
weather-compensated
control units)
73:1
to
73:6
"ON" from once per hour
for 5 min up to 6 times per
hour for 5 min during the
time program
73:7
Constantly "ON"
Heating circuit 1, heating circuit 2, heating circuit 3/Group "5"
Select
"Heating circuit ..."
for weather-compensated control units (see page 72).
Select
"5"
for constant temperature control units (see page 72).
Code 2
DHW/Group "3"
(cont.)
5457 552 GB