Coding
Coding in the delivered condition
Possible change
56:0
Set DHW temperature
adjustable from 10 to
60 °C
56:1
Set DHW temperature
adjustable from 10 to
above 60 °C
Note
Maximum value subject to
boiler coding card.
Observe the max. permis-
sible DHW temperature.
58:0
Without auxiliary function
for DHW heating
58:10
to
58:60
Input of a second set DHW
temperature, adjustable
from 10 to 60 °C (observe
coding addresses "56" and
"63")
59:0
Cylinder heating:
Starting point -2.5 K
Stopping point +2.5 K
59:1
to
59:10
Starting point adjustable
from 1 to 10 K below the set
value
5E:0
Circulation pump for cyl-
inder heating stays in
control mode at signal
"External blocking"
5E:1
Circulation pump for cylin-
der heating stops at signal
"External blocking"
5E:2
Circulation pump for cylin-
der heating starts at signal
"External blocking"
5F:0
Circulation pump for cyl-
inder heating stays in
control mode at signal
"External demand"
5F:1
Circulation pump for cylin-
der heating stops at signal
"External demand"
5F:2
Circulation pump for cylin-
der heating starts at signal
"External demand"
63:0
Without auxiliary function
for DHW heating (only for
constant temperature
control units)
63:1
Auxiliary function: 1 x daily
63:2
to
63:14
Every 2 days to every 14
days
63:15
2 x daily
Code 2
DHW/Group "3"
(cont.)