Vitocal 300, type BW 212 and WW 212 (two-stage)
A
Heating output
B
Refrigerating capacity
C
Power consumption
D
T
HV
= 35 °C
E
T
HV
= 45 °C
F
T
HV
= 55 °C
Note
COP details in the following tables and diagrams calculated with
reference to DIN EN 255.
Performance data type BW 212
Operating point
B0/W35
B2/W45
B2/W55
Heating output
kW
12.80
13.20
12.40
Refrigerating capa-
city
kW
10.00
9.60
8.20
Power consumption
kW
2.80
3.50
4.20
Coefficient of Performance
∊
(COP)
4.56
3.75
2.94
Performance data type WW 212
Operating point
W10/W35
W8/W45
W8/W55
Heating output
kW
16.80
15.20
14.20
Refrigerating capa-
city
kW
13.80
11.50
10.10
Power consumption
kW
3.00
3.70
4.50
Coefficient of Performance
∊
(COP)
5.58
4.09
3.22
5822
1
19-7
G
B
VITOCAL 300/350
VIESMANN
17
Output diagrams for the Vitocal 300 (two-stage)