Vitocal 300, type BW 232 and WW 232 (two-stage)
A
Heating output
B
Refrigerating capacity
C
Power consumption
D
T
HV
= 35 °C
E
T
HV
= 45 °C
F
T
HV
= 55 °C
Performance data type BW 232
Operating point
B0/W35
B2/W45
B2/W55
Heating output
kW
32.60
33.40
32.20
Refrigerating capa-
city
kW
25.40
24.40
21.40
Power consumption
kW
7.20
9.00
10.80
Coefficient of Performance
∊
(COP)
4.51
3.69
2.96
Performance data type WW 232
Operating point
W10/W35
W8/W45
W8/W55
Heating output
kW
43.00
39.20
37.80
Refrigerating capa-
city
kW
35.60
30.00
26.60
Power consumption
kW
7.40
9.20
11.20
Coefficient of Performance
∊
(COP)
5.79
4.24
3.35
5822
1
19-7
G
B
VITOCAL 300/350
VIESMANN
21
Output diagrams for the Vitocal 300 (two-stage)
(cont.)