Complete compact design heat pump.
With fitted, weather-compensated digital heat pump control unit,
electronic starting current limiter (not for types BW/WW 104, 106
and 212) and adjustable anti-vibration feet; colour: Vitosilver.
Additionally for type WW:

The water/water heat pump conversion kit comprises a flow limiter
and frost stat.

Weather-compensated heat pump control unit CD 60

Digital control unit for heat pump systems with integral cooling
and solar control functions, one heating circuit without mixer and
up to two heating circuits with mixer (with cooling and solar control
function, only one heating circuit with mixer), cylinder temperature
control unit for two DHW cylinders, control of an additional heat
source and control of up to 3 heat consumers.

Menu-guided operation with function-dependent plain text dis-
plays, with diagnostic system and fault display in plain text.
With outside and return temperature sensors.

Accessories

(subject to order, packed separately)

&

Divicon heating circuit distributor

&

Heating circuit pump

&

Safety equipment block with safety assembly

&

Three-way diverter valve R 1"

&

Instantaneous heating water heater

&

Heating water buffer cylinder

&

Cylinder temperature sensor

&

Remote control

&

Contact sensor

&

Mixer motor

&

Central heating mixer

&

Collector temperature sensor

&

Solar collectors

&

Natural cooling contact humidistat

&

Fan convectors Vitoclima 200-C

&

Power-OFF conversion kit

&

DHW cylinder

&

Electric immersion heater

Additional accessories for type BW/BWH

&

Brine accessories kit (assembled connection set) comprising:
Pressure switch, air distributor, safety valve (3 bar), pressure
gauge, fill and drain valves (2 pce.), fittings, shut-off valves, wall
mounting bracket, connection for an expansion vessel, brine cir-
cuit pump (supplied separately) and expansion vessel (supplied
separately)

&

Brine distributor ground collectors (10 × PE 20 × 2.0)

&

Brine distributor ground probes (4 × PE 25 × 2.3 or
4 × PE 32 × 2.9)

&

Brine circuit pressure switch

&

"Tyfocor" heat transfer medium

&

Three-way diverter valve R 1¼"

&

Plate-type heat exchanger

Additional accessories for type WW/WWH

Accessories for the groundwater circuit must be provided on site.

Design information

Positioning

Install the heat pump in a dry room free from the risk of frost.
Carry out the airtight thermal insulation of the brine side of the
heat pump installation in accordance with standard practice to
prevent condensation and corrosion.

Pipework

Never use zinc-plated/galvanised pipes for the brine circuits.

Heat transfer medium

Order the required amount of Tyfocor for the entire system.

Never

dilute the premixed heat transfer medium with water (min.

frost protection down to

15 °C).

5822

1

19-7

G

B

24

VIESMANN

VITOCAL 300/350

Delivered condition

Содержание BW 106

Страница 1: ...VITOCAL 350 Type BWH and WWH Up to 65 C flow temperature Heat pump with electric drive for DHW and central heating in mono or dual mode heating systems Brine water heat pump type BWH with 11 0 and 17 1 kW Water water heat pump type WWH type BWH plus conversion kit with 14 1 and 20 0 kW VIESMANN Datasheet Part numbers and prices see pricelist VITOCAL 300 350 Heat pump Brine Water 6 4 to 32 6 kW Wat...

Страница 2: ...of the outside temperature It can cover the entire heat demand of a building even on colder days Brine water heat pump type BW BWH with ground collector Water water heat pump type WW WWH with supply and return wells Type WW WWH heat from water The Vitocal 300 350 draws energy from groundwater where the temperature is stable and therefore achieves consistently high performance factors This means th...

Страница 3: ...quiet running through hermetically sealed Compliant scroll compressor with dual anti vibration mounts Especially suitable for low heating system temperatures e g underfloor heating Vitocal 350 with 65 C flow temperature for use in systems with radiators used in modernisation projects Weather compensated digital heat pump control unit CD 60 with integral cooling function Menu guided functions with ...

Страница 4: ...0 13 3 Starting current A 27 14 3 20 3 23 3 26 3 Starting current with stalled armature A 31 0 43 5 51 0 59 5 70 5 Fuse slow A 3 10 3 16 3 16 3 16 3 20 Protection IP 20 Control circuit rated voltage 230 V 50 Hz Fuse internal 6 3 A H slow Refrigerant circuit Refrigerant R 407 C Fill volume kg 1 9 2 2 2 6 3 1 3 4 Compressor Type Hermetically sealed scroll compressor Dimensions Total length mm 650 65...

Страница 5: ...t per compressor A 27 14 3 20 3 23 3 26 3 Starting current per compressor with stalled armature A 31 0 43 5 51 0 59 5 70 5 Fuse slow A 3 16 3 20 3 20 3 35 3 35 Protection IP 20 Control circuit rated voltage 230 V 50 Hz Fuse internal 6 3 A H slow Refrigerant circuit Refrigerant R 407C Fill volume kg 2 1 9 2 2 2 2 2 6 2 3 1 2 3 4 Compressor Type 2 hermetically sealed scroll compressors Dimensions To...

Страница 6: ...0 0 13 3 Starting current A 27 14 3 20 3 23 3 26 3 Starting current with stalled armature A 31 0 43 5 51 0 59 5 70 5 Fuse slow A 3 10 3 16 3 16 3 16 3 20 Protection IP 20 Control circuit rated voltage 230 V 50 Hz Fuse internal 6 3 A H slow Refrigerant circuit Refrigerant R 407 C Fill volume kg 1 9 2 2 2 6 3 1 3 4 Compressor Type Hermetically sealed scroll compressor Dimensions Total length mm 650 ...

Страница 7: ...current per compressor A 27 14 3 20 3 23 3 26 3 Starting current per compressor A 31 0 43 5 51 0 59 5 70 5 with stalled armature Fuse slow A 3 16 3 20 3 20 3 35 3 35 Protection IP 20 Control circuit rated voltage 230 V 50 Hz Fuse internal 6 3 A H slow Refrigerant circuit Refrigerant R 407 C Fill volume kg 2 1 9 2 2 2 2 2 6 2 3 1 2 3 4 Compressor Type 2 hermetically sealed scroll compressors Dimens...

Страница 8: ... 59 5 70 5 with stalled armature Fuse slow A 3 20 3 20 Protection IP 20 Control circuit rated voltage 230 V 50 Hz Fuse internal 6 3 A H slow Refrigerant circuit Refrigerant R 407 C Fill volume kg 2 9 3 2 Compressor Type Hermetically sealed scroll compressor with injection Dimensions Total length mm 650 650 Total width mm 600 600 Total height mm 945 945 Permissible operating pressure Brine circuit ...

Страница 9: ... 5 70 5 with stalled armature Fuse slow A 3 20 3 20 Protection IP 20 Control circuit rated voltage 230 V 50 Hz Fuse internal 6 3 A H slow Refrigerant circuit Refrigerant R 407 C Fill volume kg 2 9 3 2 Compressor Type Hermetically sealed scroll compressor with injection Dimensions Total length mm 650 650 Total width mm 600 600 Total height mm 945 945 Permissible operating pressure Groundwater circu...

Страница 10: ...ation Vitocal 300 350 single stage right illustration Vitocal 300 two stage A Primary OUT brine B Primary IN brine C Cable entries HR Heating return HV Heating flow 5822 119 7 GB 10 VIESMANN VITOCAL 300 350 Specification cont ...

Страница 11: ...Wall clearances 5822 119 7 GB VITOCAL 300 350 VIESMANN 11 Specification cont ...

Страница 12: ...35 B2 W45 B2 W55 Heating output kW 6 40 6 60 6 20 Refrigerating capa city kW 5 00 4 80 4 10 Power consumption kW 1 40 1 75 2 10 Coefficient of Performance COP 4 57 3 76 2 95 Performance data type WW 106 Operating point W10 W35 W8 W45 W8 W55 Heating output kW 8 40 7 60 7 30 Refrigerating capa city kW 6 90 5 75 5 05 Power consumption kW 1 50 1 85 2 25 Coefficient of Performance COP 5 60 4 11 3 24 58...

Страница 13: ...Refrigerating capa city kW 6 50 6 25 5 30 Power consumption kW 1 80 2 25 2 75 Coefficient of Performance COP 4 61 3 77 2 95 Performance data type WW 108 Operating point W10 W35 W8 W45 W8 W55 Heating output kW 10 90 9 90 9 50 Refrigerating capa city kW 9 00 7 55 6 65 Power consumption kW 1 90 2 35 2 85 Coefficient of Performance COP 5 74 4 21 3 33 5822 119 7 GB VITOCAL 300 350 VIESMANN 13 Output di...

Страница 14: ...Refrigerating capa city kW 8 40 8 10 7 00 Power consumption kW 2 40 3 00 3 60 Coefficient of Performance COP 4 50 3 70 2 94 Performance data type WW 110 Operating point W10 W35 W8 W45 W8 W55 Heating output kW 14 20 12 90 12 40 Refrigerating capa city kW 11 70 9 80 8 68 Power consumption kW 2 50 3 10 3 75 Coefficient of Performance COP 5 68 4 16 3 31 5822 119 7 GB 14 VIESMANN VITOCAL 300 350 Output...

Страница 15: ...frigerating capa city kW 10 95 10 65 9 35 Power consumption kW 3 05 3 75 4 55 Coefficient of Performance COP 4 59 3 84 3 05 Performance data type WW 113 Operating point W10 W35 W8 W45 W8 W55 Heating output kW 18 30 16 70 16 10 Refrigerating capa city kW 15 20 12 85 11 40 Power consumption kW 3 10 3 85 4 70 Coefficient of Performance COP 5 90 4 34 3 43 5822 119 7 GB VITOCAL 300 350 VIESMANN 15 Outp...

Страница 16: ...rigerating capa city kW 12 70 12 20 10 70 Power consumption kW 3 60 4 50 5 40 Coefficient of Performance COP 4 53 3 71 2 98 Performance data type WW 116 Operating point W10 W35 W8 W45 W8 W55 Heating output kW 21 50 19 60 18 90 Refrigerating capa city kW 17 80 15 00 13 30 Power consumption kW 3 70 4 60 5 60 Coefficient of Performance COP 5 81 4 26 3 37 5822 119 7 GB 16 VIESMANN VITOCAL 300 350 Outp...

Страница 17: ... W45 B2 W55 Heating output kW 12 80 13 20 12 40 Refrigerating capa city kW 10 00 9 60 8 20 Power consumption kW 2 80 3 50 4 20 Coefficient of Performance COP 4 56 3 75 2 94 Performance data type WW 212 Operating point W10 W35 W8 W45 W8 W55 Heating output kW 16 80 15 20 14 20 Refrigerating capa city kW 13 80 11 50 10 10 Power consumption kW 3 00 3 70 4 50 Coefficient of Performance COP 5 58 4 09 3 ...

Страница 18: ...rigerating capa city kW 13 00 12 50 10 60 Power consumption kW 3 60 4 50 5 50 Coefficient of Performance COP 4 60 3 76 2 94 Performance data type WW 216 Operating point W10 W35 W8 W45 W8 W55 Heating output kW 21 80 18 80 19 00 Refrigerating capa city kW 18 00 15 10 13 30 Power consumption kW 3 80 4 70 5 70 Coefficient of Performance COP 5 72 4 19 3 31 5822 119 7 GB 18 VIESMANN VITOCAL 300 350 Outp...

Страница 19: ...rigerating capa city kW 16 80 16 20 14 00 Power consumption kW 4 80 6 00 7 20 Coefficient of Performance COP 4 49 3 69 2 93 Performance data type WW 220 Operating point W10 W35 W8 W45 W8 W55 Heating output kW 28 40 25 80 24 80 Refrigerating capa city kW 23 40 19 60 17 30 Power consumption kW 5 00 6 20 7 50 Coefficient of Performance COP 5 66 4 14 3 29 5822 119 7 GB VITOCAL 300 350 VIESMANN 19 Outp...

Страница 20: ...rigerating capa city kW 21 90 21 30 18 70 Power consumption kW 6 10 7 50 9 10 Coefficient of Performance COP 4 57 3 82 3 00 Performance data type WW 226 Operating point W10 W35 W8 W45 W8 W55 Heating output kW 36 60 33 40 32 20 Refrigerating capa city kW 30 40 25 70 22 80 Power consumption kW 6 20 7 70 9 40 Coefficient of Performance COP 5 87 4 31 3 40 5822 119 7 GB 20 VIESMANN VITOCAL 300 350 Outp...

Страница 21: ...igerating capa city kW 25 40 24 40 21 40 Power consumption kW 7 20 9 00 10 80 Coefficient of Performance COP 4 51 3 69 2 96 Performance data type WW 232 Operating point W10 W35 W8 W45 W8 W55 Heating output kW 43 00 39 20 37 80 Refrigerating capa city kW 35 60 30 00 26 60 Power consumption kW 7 40 9 20 11 20 Coefficient of Performance COP 5 79 4 24 3 35 5822 119 7 GB VITOCAL 300 350 VIESMANN 21 Out...

Страница 22: ... W35 B2 W55 B2 W65 Heating output kW 11 00 13 20 13 20 Refrigerating capa city kW 8 45 9 00 8 10 Power consumption kW 2 55 4 20 5 10 Coefficient of Performance COP 4 31 3 14 2 59 Performance data type WWH 110 Operating point W10 W35 W8 W55 W8 W65 Heating output kW 14 10 14 60 14 90 Refrigerating capa city kW 11 40 10 30 9 45 Power consumption kW 2 70 4 30 5 15 Coefficient of Performance COP 5 22 3...

Страница 23: ... 70 Refrigerating capa city kW 12 45 12 00 10 60 Power consumption kW 3 75 5 70 7 10 Coefficient of Performance COP 4 32 3 11 2 49 Performance data type WWH 113 Operating point W10 W35 W8 W55 W8 W65 Heating output kW 19 70 19 40 19 40 Refrigerating capa city kW 15 90 13 65 12 15 Power consumption kW 3 80 5 75 7 25 Coefficient of Performance COP 5 18 3 37 2 68 5822 119 7 GB VITOCAL 300 350 VIESMANN...

Страница 24: ...al heating mixer Collector temperature sensor Solar collectors Natural cooling contact humidistat Fan convectors Vitoclima 200 C Power OFF conversion kit DHW cylinder Electric immersion heater Additional accessories for type BW BWH Brine accessories kit assembled connection set comprising Pressure switch air distributor safety valve 3 bar pressure gauge fill and drain valves 2 pce fittings shut of...

Страница 25: ...pumps up to a rated heat output of 16 kW we recom mend the installation of the Vitocell 100 V type CVW DHW cylin der with 390 l capacity for further details see the separate datasheet For heat pumps with a rated heat output in excess of 16 kW we recommend the installation of a cylinder primary system with a Vitocell 100 V type CVA from 300 l capacity in conjunction with a Vitotrans 100 plate type ...

Страница 26: ...w viessmann com Subject to technical modifications Viessmann Limited Hortonwood 30 Telford Shropshire TF1 7YP GB Telephone 44 1952 675000 Fax 44 1952 675040 E mail info uk viessmann com 5822 119 7 GB Printed on environmentally friendly chlorine free bleached paper 26 VIESMANN VITOCAL 300 350 ...

Отзывы: