Vitocal 300, type BW 113 and WW 113 (single stage)
A
Heating output
B
Refrigerating capacity
C
Power consumption
D
T
HV
= 35 °C
E
T
HV
= 45 °C
F
T
HV
= 55 °C
Performance data type BW 113
Operating point
B0/W35
B2/W45
B2/W55
Heating output
kW
14.00
14.40
13.90
Refrigerating capa-
city
kW
10.95
10.65
9.35
Power consumption
kW
3.05
3.75
4.55
Coefficient of Performance
∊
(COP)
4.59
3.84
3.05
Performance data type WW 113
Operating point
W10/W35
W8/W45
W8/W55
Heating output
kW
18.30
16.70
16.10
Refrigerating capa-
city
kW
15.20
12.85
11.40
Power consumption
kW
3.10
3.85
4.70
Coefficient of Performance
∊
(COP)
5.90
4.34
3.43
5822
1
19-7
G
B
VITOCAL 300/350
VIESMANN
15
Output diagrams for the Vitocal 300 (single stage)
(cont.)