Transportation
16
Assembly instructions
VITOBLOC 200 BM-190/238
5780045
GB
3.4
Setting up
●
The cogeneration module is installed on a raised
base without separate anchoring and placed on
sylomer strips (loose supply) for separation from
structure-borne noise.
CAUTION
Make sure that the foundation base has
the required height (≥ 150 mm) for
drainage of condensed water.
H
W
L
Fig. 4
block-type thermal power plant with base
Switching
cabinet
side
3600
1
6
0
0
Fig. 5
Locating plan for sylomer strips
Minimum base size for Vitobloc 200 BM-190/238
L
3,600 mm
W
1,600 mm
H
150 mm
The scope of delivery includes:
7 green SR 55 sylomer strips
(1,500 x 100 x 50 mm)
blank required:
6 x 1,500 mm long
2 x 500 mm long