Coding in the delivered condition
Possible change
b2:8
With remote control and for the
heating circuit, operation with room
temperature hook-up must be pro-
grammed: Room influence factor 8
(only for weather-compensated
control units; only change the code
for the heating circuit with mixer)
b2:0
Without room influence
b2:1
to
b2:64
Room influence factor adjustable
from 1 to 64. The higher the value,
the greater the room influence.
b5:0
With remote control: No room tem-
perature-dependent heating circuit
pump logic function (only for
weather-compensated control
units; only change the code for the
heating circuit with mixer)
b5:1
to
b5:8
For heating circuit pump logic func-
tion, see the following table:
Parameter address
b5:...
With heating circuit pump logic function:
Heating circuit pump "OFF"
Heating circuit pump "ON"
1
RT
actual
>
RT
set
+ 5 K
RT
actual
< RT
set
+ 4 K
2
RT
actual
>
RT
set
+ 4 K
RT
actual
< RT
set
+ 3 K
3
RT
actual
>
RT
set
+ 3 K
RT
actual
< RT
set
+ 2 K
4
RT
actual
>
RT
set
+ 2 K
RT
actual
< RT
set
+ 1 K
5
RT
actual
>
RT
set
+ 1 K
RT
actual
< RT
set
6
RT
actual
>
RT
set
RT
actual
< RT
set
–
1 K
7
RT
actual
>
RT
set
–
1 K
RT
actual
< RT
set
–
2 K
8
RT
actual
>
RT
set
–
2 K
RT
actual
< RT
set
–
3 K
Coding in the delivered condition
Possible change
C5:20
Electronic minimum flow tempera-
ture limit 20 °C (only for weather-
compensated control units)
C5:1
to
C5:127
Minimum limit adjustable from 1 to
127 °C (limited by boiler-specific pa-
rameters)
C6:74
Electronic maximum flow tempera-
ture limit 74 °C (only for weather-
compensated control units)
C6:10
to
C6:127
Maximum limit adjustable from 10 to
127 °C (limited by boiler-specific pa-
rameters)
d3:14
Heating curve slope = 1.4
d3:2
to
d3:35
Heating curve slope adjustable from
0.2 to 3.5 (see page 39)
d4:0
Heating curve level = 0
d4:–13
to
d4:40
Heating curve level adjustable from
–
d5:0
The external operating program
changeover switches the operating
program to "Constant operation
with reduced room temperature" or
"Standby mode" (only for weather-
compensated control units)
d5:1
The external operating program
changeover switches to "Constant
operation with standard room tem-
perature" (subject to coding address
3A, 3b and 3C)
d6:0
Heating circuit pump stays in con-
trol mode at signal "External block-
ing"
d6:1
Heating circuit pump stops at signal
"External blocking" (subject to cod-
ing addresses 3A, 3b and 3C)
d6:2
Heating circuit pump starts at signal
"External blocking" (subject to cod-
ing addresses 3A, 3b and 3C)
Code 2
"Heating circuit ..."/Group 5
(cont.)
5772 980 GB