50
Coding in the delivered condition
Possible change
Heating program changeover
d5:0
The external operating program
changeover switches the operating
program to "Constant operation
with reduced room temperature" or
"Standby mode" (only for weather-
compensated control units)
d5:1
The external operating program
changeover switches to "Constant
operation with standard room tem-
perature" (subject to coding address
3A, 3b and 3C)
Ext. heating program changeover to heating circuit
d8:0
No operating program changeover
via extension EA1
d8:1
Operating program changeover via
input DE1 at extension EA1
d8:2
Operating program changeover via
input DE2 at extension EA1
d8:3
Operating program changeover via
input DE3 at extension EA1
Max. pump speed in standard mode
E6:...
Only for heating systems without a
heating circuit with mixer:
Maximum speed of the internal
variable speed heating circuit
pump in % of the max. speed in
standard mode. Value is specified
by boiler-specific parameters (only
for weather-compensated control
units).
E6:0
to
E6:100
Maximum speed adjustable from 0
to 100 %
Min. pump speed
E7:30
Only for heating systems without a
heating circuit with mixer:
Minimum speed of the internal var-
iable speed heating circuit pump:
30 % of max. speed (only for
weather-compensated control
units)
E7:0
to
E7:100
Minimum speed adjustable from 0 to
100 % of the maximum speed
Screed drying
F1:0
Screed drying disabled (only for
weather-compensated control
units).
F1:1
to
F1:6
Screed drying adjustable in accord-
ance with 6 selectable temperature/
time profiles (see page 98)
F1:15
Constant flow temperature 20 °C
Party mode time limit
F2:8
Time limit for party mode or exter-
nal operating program changeover
via key: 8 h (only for weather-com-
pensated control units)
*1
F2:0
No time limit for party mode
*1
F2:1
to
F2:12
Time limit adjustable from 1 to 12 h
*1
Pump control in "Only DHW"
F6:25
In the "Only DHW" operating
mode, the internal circulation pump
is permanently on (only for con-
stant temperature control units)
F6:0
In the "Only DHW" operating mode,
the internal circulation pump is per-
manently off
F6:1
to
F6:24
In operating mode "DHW only", the
internal circulation pump will be star-
ted 1 to 24 times per day for 10 min
each time.
*1
In the "Heating and DHW" program, party mode ends
automatically
when the system changes over to operation with
standard room temperature.
Code 1
"Heating circuit ..."/Group 5
(cont.)
5772 980 GB
Service