Heating program - changeover
Code
Changeover via input DE1
d8:1
Changeover via input DE2
d8:2
Changeover via input DE3
d8:3
You can select which direction the heating program
changeover takes in coding address "d5" in the
"Heat-
ing circuit"
group:
Heating program - changeover
Code
Changeover towards "Permanently reduced" or "Permanent standby" mode (sub-
ject to the selected set value)
d5:0
Changeover towards "Constant heating mode"
d5:1
The duration of the heating program changeover is set
via coding address "F2" in the
"Heating circuit"
group:
Heating program - changeover
Code
No operating program changeover
F2:0
Duration of the operating program changeover 1 to 12 hours
F2:1 to
F2:12
The operating program changeover stays enabled for
as long as the contact remains closed, but at least as
long as the duration selected in coding address "F2".
External blocking
The "External blocking" and "External blocking and
fault message input" functions are connected via
extension EA1. There are 3 inputs available at exten-
sion EA1 (DE1 to DE3).
The function is selected via the following coding
addresses in the
"General"
group:
External blocking
Code
Input DE1
3A:3
Input DE2
3b:3
Input DE3
3C:3
External blocking and fault message input
Code
Input DE1
3A:4
Input DE2
3b:4
Input DE3
3C:4
The effect on the internal circulation pump is selected
in coding address "3E" in group
"General"
.
The effect on the relevant heating circuit pump is
selected in coding address "d6" in group
"Heating cir-
cuit"
.
External demand
The "External demand" function is connected via
extension EA1. There are 3 inputs available at exten-
sion EA1 (DE1 to DE3).
The function is selected via the following coding
addresses in the
"General"
group:
Function description
Control functions
(cont.)