56
Coding in the delivered condition
Possible change
53:3
Function terminal
sK
: External circu-
lation pump for cylinder heating
54:0
Without solar thermal system
54:1
With Vitosolic 100 (automatic recog-
nition)
54:2
With Vitosolic 200 (automatic recog-
nition)
54:3
No function
54:4
With solar control module SM1 with
auxiliary function, e.g. central heat-
ing backup (automatic recognition)
6E:50
No display correction for outside
temperature.
6E:0
to
6E:49
Display correction
–
5 K to
–
0.1 K
6E:51
to
6E:100
Display corr0.1 K to +5 K
76:0
Without LON communication mod-
ule (only for weather-compensated
control units)
76:1
With LON communication module
(automatic recognition)
77:1
LON subscriber number (only for
weather-compensated control
units)
77:2
to
77:99
LON subscriber number, adjustable
from 1 to 99:
1 - 4 = Boiler
5 = Cascade
10 - 97 = Vitotronic 200-H
98 = Vitogate
99 = Vitocom
Note
Allocate each number only
once
.
79:1
With LON communication module:
Control unit is fault manager (only
for weather-compensated control
units)
79:0
Control unit is not fault manager
7b:1
With LON communication module:
Control unit transmits the time (on-
ly for weather-compensated con-
trol units)
7b:0
Does not transmit time
7F:1
Detached house (only for weather-
compensated control units)
7F:0
Apartment building
Separate adjustment of holiday pro-
gram and time program for DHW
heating possible
80:6
If a fault occurs for at least 30 s, a
fault message is displayed
80:0
Immediate fault message
80:2
to
80:199
Minimum fault duration until fault
message occurs, adjustable from
10 s to 995 s; 1 step
≙
5 s
81:1
Automatic summer/wintertime
changeover
81:0
Manual summer/wintertime change-
over
81:2
Use of the radio clock receiver (au-
tomatic recognition)
81:3
With LON communication module:
The control unit receives the time
Code 2
"General"/Group 1
(cont.)
5772 980 GB
Service