71
External blocking of compressor and pumps
Parameter
Setting
"System definition"
Ó
"Effect of external blocking on pumps/compressor 701A"
"0"
to
"31"
External blocking of the compressor; mixer in control mode or CLOSED
Parameter
Setting
"System definition"
Ó
"Effect of ext. blocking on heat pump/heating circuits 7015"
"0"
to
"8"
"Effect of external blocking on pumps/compressor 701A"
"0"
to
"31"
Type AWB(-M)-E-AC: Cooling function parameters
Parameter
Setting
"Cooling"
Ó
"Cooling function 7100"
"3"
"Cooling circuit 7101"
"1"
Heating circuit HC1
"2"
Heating circuit HC2
"3"
Heating circuit HC3
"4"
Separate cooling circuit SKK
Parameters for solar DHW heating
Parameters in conjunction with solar control module type SM1
Setting
"Solar"
Ó
"Type solar control unit 7A00"
"3"
Parameter C0xx
See installation and service instruc-
tions for "Solar control module, type
SM1".
Parameters for instantaneous heating water heater
Parameter
Setting
"Electr booster heater"
Ó
"Enable instantaneous heating water heater 7900"
"1"
"Output for instant. heating water heater at power-OFF 790A" "1"
3 kW
"2"
6 kW
"3"
9 kW
Enable instantaneous heating water heater for DHW heating
Parameter
Setting
"DHW"
Ó
"Enable electric heaters for DHW heating 6015"
"1"
Parameters for external heat generators
Parameter
Setting
"External heat source"
Ó
"Enable external heat source 7B00"
"1"
Commissioning, inspection, maintenance
Commissioning the system
(cont.)
5790 931 GB