133
Cooling
Parameter
Code
Delivered condition Commission-
ing
Maintenance/
service
"Cooling function"
7100
0
"Cooling circuit"
7101
1
"Set room temperature separate cooling
circuit"
7102
200 (
≙
20 °C)
"Min. flow temperature cooling"
7103
200 (
≙
20 °C)
"Influence room temperature hook-up
cooling circuit"
7104
0
"Room temperature control cooling cir-
cuit"
7105
1
"Ranking room temp sensor separate
cooling circuit"
7106
0
"Hysteresis room temp cooling circuit"
7107
10 (
≙
1 K)
"Enable flow temperature sensor cooling
circuit"
7109
1
"Cooling curve level"
7110
0 (
≙
0 K)
"Cooling curve slope"
7111
12 (
≙
1.2)
"Remote control cooling circ"
7116
Never adjust
"Enable active cooling"
71FE
0
Ventilation: Vitovent 200-C and Vitovent 300-F
Parameter
Code
Delivered condition Commission-
ing
Maintenance/
service
"Vitovent enable"
7D00
0
"Enable preheater bank electric"
7D01
0
"Enable reheater bank hydraulic"
7D02
0
"Enable target temperature control"
7D04
0
"Enable humidity sensor"
7D05
0
"Enable CO2 sensor"
7D06
0
"Set extract air temperature"
7D08
200 (
≙
20 °C)
"Flow rate reduced ventilation"
7D0A
■
Vitovent 200-C:
75 m
3
/h
■
Vitovent 300-F:
120 m
3
/h
"Flow rate nominal ventilation"
7D0B
■
Vitovent 200-C:
115 m
3
/h
■
Vitovent 300-F:
170 m
3
/h
"Flow rate intensive ventilation"
7D0C
■
Vitovent 200-C:
155 m
3
/h
■
Vitovent 300-F:
215 m
3
/h
"Min. supply air temperature for bypass"
7D0F
160 (
≙
16 °C)
"CO2 value for raising the flow rate"
7D18
800 ppm
"Humidity value for raising the flow rate"
7D19
65 %
"Interval time frost protection ventila-
tion"
7D1A
15 min
"Intensive ventilation duration"
7D1B
120 min
"Actual source room temperature"
7D1D
1
Commissioning/service reports
Control parameter report
(cont.)
5790 931 GB
Appendix