81
Energy meter
Electricity meter parameters
Setting
"Photovoltaics"
Ó
"Enable own energy consumption PV 7E00"
"1"
"Photovoltaics"
Ó
"Threshold for electrical power 7E04"
"0"
to
"300"
(
≙
0 to 30 kW)
Extended menu:
"PV ctrl strategy"
or
"Photovoltaics"
Ó
Enable required functions for on-
site power consumption.
■
"Enable own energy consumptn for set DHW
temperature 2 7E10"
"1"
■
"Enable own energy consumption for DHW
heating 7E11"
"1"
■
"Enable own energy consumptn for heating
water buffer cyl. 7E12"
"1"
■
"Enable own energy consumption for heat-
ing 7E13"
"1"
Extended menu:
"PV ctrl strategy"
or
"Photovoltaics"
Ó
Specify the temperature differen-
tial to the selected set value for
the chosen function.
■
"Raise set DHW cylinder temperature PV
7E21"
"0"
to
"200"
(
≙
0 to 20 °C)
■
"Raise set heating water buffer cylinder
temp PV 7E22"
"0"
to
"100"
(
≙
0 to 10 °C)
■
"Raise set room temperature PV 7E23"
"0"
to
"50"
(
≙
0 to 5 °C)
Ventilation
Ventilation unit parameters
Setting
"Ventilation"
Ó
"Vitovent enable 7D00"
"1"
Other enabling settings, if applicable:
"Ventilation"
Ó
■
"Enable preheater bank electric 7D01"
"1"
■
"Enable reheater bank hydraulic 7D02"
"1"
■
"Enable humidity sensor 7D05"
"1"
■
"Enable CO2 sensor 7D06"
"1"
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)
5546 267 GB
Service
Содержание 7514659
Страница 30: ...30 Installing the programming unit 2x 3 2 1 Installation sequence Electrical connections 5546 267 GB...
Страница 67: ...67 A Installation sequence Checking diaphragm grommets cont 5546 267 GB Installation...
Страница 84: ...84 Overview of electrical components Type BW 351 A18 D L K H G F E C B A Troubleshooting Repairs 5546 267 GB...
Страница 138: ...138 5546 267 GB...
Страница 139: ...139 5546 267 GB...