90
Low-noise version
Type
HE90-LN
HE120-LN
HE140-LN
HE190-LN
Electrical values
Rated voltage
3L/N/PE 400 V/50 Hz
Maximum power consumption
kW
0.8
1.1
1.3
1.2
MCB/fuse protection (on site)
A
6
6
6
6
Maximum operating current
A
1.2
2.4
2.4
2.1
IP rating
IP 54
IP 54
IP 54
IP 54
Fan speed
rpm
360
347
390
320
No. of fans
Pce.
6
8
10
16
Dimensions
Total length
mm
4164
5429
6694
10489
Total width
mm
2300
2300
2300
2300
Total height
mm
2532
2532
2532
2532
Dry weight
kg
1535
2003
2511
3948
Heat exchanger capacity
l
231
307
384
597
Connections
Inlet air/brine heat exchanger (flange)
2 x DN 50/
PN 10
2 x DN 50/
PN 10
2 x DN 65/
PN 10
2 x DN 65/
PN 10
Outlet air/brine heat exchanger (flange)
2 x DN 50/
PN 10
2 x DN 50/
PN 10
2 x DN 65/
PN 10
2 x DN 65/
PN 10
Sound
Sound power
dB(A)
62
62
65
64
Sound pressure (10 m free field)
dB(A)
30
30
30
30
Note
The technical information in the datasheets and prod-
uct description describe purely physical characteristics.
Additional assurances or guarantees require a sepa-
rate contractual agreement.
Specification
Specification, air/brine heat exchanger
(cont.)