41
Clamps
Function
Explanation
204XD3
1: Start command EB
2: Start command EB
3: Set value 0-10 V
4: GND
5: Operating message
COM
6: Operating message NO
PE: Shield connection
Circulation pump control signals,
heat exchanger, defrosting, resid-
ual heat, brine
Floating N/O contact:
Closed: Demand, circulation pump, heat ex-
changer defrosting, residual heat, brine
Open:
No demand
Signal 0 to 10 V
Contact closed:
Circulation pump operation, heat exchanger de-
frosting, residual heat, brine
205XD1
1: External conductor L1
2: External conductor L2
3: External conductor L3
N: Neutral conductor
PE: Earth conductor
Circulation pump load, heat ex-
changer defrosting, residual heat,
water
Circuit protection from load fuse 104FC3 (ob-
serve the total current of max. 16 A)
Connection values:
■
Max. output: 4000 W/2200 W
■
Voltage: 400 V~/230 V~
205XD3
1: Start command EB
2: Start command EB
3: Set value 0-10 V
4: GND
5: Operating message
COM
6: Operating message NO
PE: Shield connection
Circulation pump control signals,
heat exchanger, defrosting, resid-
ual heat, water
Floating N/O contact:
Closed: Demand, circulation pump heat ex-
changer defrosting, residual heat, water
Open:
No demand
Signal 0 to 10 V
Contact closed:
Circulation pump operation, heat exchanger de-
frosting, residual heat, water
206XD1
1: External conductor L1
2: External conductor L2
3: External conductor L3
N: Neutral conductor
PE: Earth conductor
Circulation pump load, external
heat generator
Circuit protection from load fuse 104FC3 (ob-
serve the total current of max. 16 A)
Connection values:
■
Max. output: 4000 W/2200 W
■
Voltage: 400 V~/230 V~
206XD3
1: Start command EB
2: Start command EB
3: Operating message
COM
4: Operating message NO
Circulation pump control signals,
external heat generator
Floating N/O contact:
Closed: Demand, circulation pump, external
heat generator
Open:
No demand
Contact closed:
Circulation pump operation, external heat gener-
ator
207XD1
1: External conductor L1
2: External conductor L2
3: External conductor L3
N: Neutral conductor
PE: Earth conductor
Circulation pump load, NC charge Circuit protection from load fuse 104FC3 (ob-
serve the total current of max. 16 A)
Connection values:
■
Max. output: 4000 W/2200 W
■
Voltage: 400 V~/230 V~
207XD3
1: Start command EB
2: Start command EB
3: Operating message
COM
4: Operating message NO
Circulation pump control signals,
NC charge
Floating N/O contact:
Closed: Demand, circulation pump NC charge
Open:
No demand
Contact closed:
Circulation pump operation NC charge
Installation procedure, heat pump
Electrical connections
(cont.)
5837251
Installation