68
Service
System info
Enter password
Last operation:
Last fault:
1327
Size:
BW302.B120
SW version:
V0.96R43
IP address:
Select language
System
Start page
0
1327
20140812
Plant switched on
Start page
Menu
Heating mode:
Cascade
Master
10
1
1
93
Log off
Configuration
Demo Mode
User level 2
Fig.54
■
Enter the service password
■
Select
"Configuration"
■
Select
"Parameters of sys.controller"
■
Then select
"Cascade settings"
The following screen appears:
Heat pump configuration cascade
Plant switched on
Cascade:
Start page
Menu
Cascade present
Yes
This heat pump is
Slave1
Heat pump 2 / slave 1
Modbus address
Heat pump heating mode
Ethernet address
Heating circuit extension
Communication cascade
Activate cascade
Communication interval
Yes
240
Emergency mode only
0
0
0
0
Fig.55
Configuration of slave heating circuits
■
Select cylinder heating. The cylinder is displayed
with the slave heat pump, but is disabled. The cylin-
der is always checked by the master heat pump
■
All 3 heating circuits can be configured
■
The heating circuits that are connected to the slave
heat pump must also be set at and monitored by the
slave heat pump
■
The outside temperature is only captured by the
master heat pump. The actual value is transmitted to
the slave heat pump. Offset and message must be
set separately at the slave heat pump
Commissioning, inspection, maintenance
Commissioning the system
(cont.)
5549 991 GB