36
Terminal strip for internal heat pump components
Terminals
Function
Explanation
2X8
Oil sump heater compressor 1, acces-
sories
Connection values
■
Max. output:
140 W
■
Voltage:
230 V
∼
Factory-fitted
3X8
Oil sump heater compressor 2, acces-
sories
Connection values
■
Max. output:
140 W
■
Voltage:
230 V
∼
Factory-fitted
8X1
Winding protection compressor 1
Connection values
■
Voltage:
24 VDC/230 VAC
Factory-fitted
8X3
High pressure sensor compressor 1
Connection values
■
Voltage:
24 VDC/230 VAC
Factory-fitted
9X1
Winding protection compressor 2
Connection values
■
Voltage:
24 VDC/230 VAC
Factory-fitted
9X3
High pressure sensor compressor 2
Connection values
■
Voltage:
24 VDC/230 VAC
Factory-fitted
13X6
EEV control valve, liquid
Evaporator
Heat yield
Electronic expansion valve (EEV), Sie-
mens
Factory-fitted
Danger
Incorrectly executed electrical installations can
result in injuries from electrical current and in
appliance damage.
All sensor leads and 0-10 V signal leads must
be shielded with copper braiding and have a
minimum cross-section of 0.5 mm².
Specified lead type: CV.
Sensors
Terminals
Sensor
Type
15X2
Outside temperature sensor
Pt 1000 (PTC)
27X1
Temperature sensor
cylinder heating, top
Pt 1000 (PTC)
Installation sequence
Overview of electrical connections
(cont.)
5549 991 GB
Installation