Use
Gas installation
Liquid gas installation
Heating oil and diesel
pipelines
Operating temperature
-20 °C up to +70 °C
-20 °C up to +70 °C
≤
40 °C
Operating pressure
≤
0.5 MPa (5 bar)
(MOP 5)
≤
0.1 MPa (1 bar) (HTR /
GT1)
2)
≤
0.5 MPa (5 bar)
(MOP 5)
1)
≤
0.1 MPa (1 bar) (HTR /
GT1)
2)
≤
0.5 MPa (5 bar)
1)
The maximum pressure equates to the pick-up pressure of the SSV in the pressure regulating valve.
2)
GT1: Operating pressure at HTR requirement 650 °C / 30 min max. 0.1 MPa (1 bar)
2.3.5
Markings on components
Fig. 4: Marking on the press connector
The press connectors are marked as follows:
n
yellow rectangle for gas
n
Gas for gas supply lines
n
MOP5 for maximum operating pressure 0.5 MPa (5 bar)
n
GT1 for operating pressure with HTR requirement 0.1 MPa (1 bar)
n
DVGW
Markings on press connectors
Product information
Profipress G XL
13 from 23