PI-PR-560400 0412 (Basic Digital Setpoint Control II)

2 of 4

Viega... The global leader in plumbing, heating and pipe joining systems

301 N. Main, 9th Floor • Wichita, KS 67202 • Ph: 800-976-9819 • Fax: 316-425-7618 • www.viega.com

©2012, ProPress

®

, FostaPEX

®

, GeoFusion

®

, Seapress

®

 MegaPress

®

, MegaPressG

®

, and Viega

®

 are registered trademarks of Viega GmbH & Co. PureFlow

®

, Smart Connect

®

, Climate Panel

®

, Climate Mat

®

, Climate 

Trak

®

, MANABLOC

®

, Radiant Wizard

®

, S-no-Ice

®

, Snap Panel

®

, XL

®

 and XL-C

®

 are registered trademarks of Viega LLC.  MiniBloc

, Rapid Grid

, ProRadiant

, PolyAlloy

, SmartLoop

 and Zero Lead

 are trademarks 

of Viega LLC; ProPressG

 and ViegaPEX

 are trademarks of Viega GmbH & Co. KG.  RIDGID

®

 is a registered trademark of RIDGID, Inc.

Product

Instructions

Installation

Digital Setpoint Control II (17029)

Watertight Sensor (17031)

For proper control, the sensor for 
the  setpoint control must be located 
within the heating and or cooling slab.  
The sensor should be placed midway          
between rows of tubing, and should be 
placed in conduit which is cast into the 
slab, so that replacement is possible.

SENSOR B

SENSOR A
SENSOR B

24VAC 

SUPPLY 

120V,  240V        

  SUPPLY 

RELAY 1 RELAY 2

Digital Input

LOAD 2

LOAD 1

Wiring

Sensor A is triggering the two relays, 
Relay 1 being boiler circulator pump, 
and Relay 2 being system circulator 
pump.  In heating mode, when the 
sensor detects temperature lower than 
the selected setpoint minus the selected 
differential both relays will be energized. 
When the temperature reaches the 
setpoint the relays will de-energize.

Note: 
If using 24V to power the controller,  
the 24V supply must be connected to 
terminals that are , C on the 
left side of the control.

If using 120 or 240V to power the 
controller the 120 or 240V supply must 
be connect to corresponding terminals 
clearly marked on the right side of the 
control. When connecting the sensor 
connect both red wires to one terminal 
and the white wire to the other terminal. 
Terminals for sensor marked "T".

120 V

COM

Содержание Basic Digital Setpoint Control II

Страница 1: ...e control with a wide range of applications in the HVAC industry This control provides two isolated SPDT relay contacts The two relays are controlled by a watertight sensor included with the Basic Digital Setpoint Control This control is commonly used as basic heating and or cooling system control for commercial and residential slab applications Features Setpoint Control for Heating and Cooling Si...

Страница 2: ...eating and or cooling slab The sensor should be placed midway between rows of tubing and should be placed in conduit which is cast into the slab so that replacement is possible SENSOR B SENSOR A SENSOR B 24VAC SUPPLY 120V 240V SUPPLY RELAY 1 RELAY 2 Digital Input LOAD 2 LOAD 1 Wiring Sensor A is triggering the two relays Relay 1 being boiler circulator pump and Relay 2 being system circulator pump...

Страница 3: ...djusted press the right arrow button to accept and to display the Relay 1 menu 6 Select Diffrntl by pressing the right arrow button 7 Using the up and down arrows adjust the differential the range is 1 150 F once selected press the right arrow to accept and return to Relay 1 menu 8 Select Sensor A or Sensor B for Relay 1 using the up and down arrows then press right arrow button to accept 9 Select...

Страница 4: ...stered trademark of RIDGID Inc Product Instructions Troubleshooting If the system is not operating correctly first check that all electrical connections have been made properly Check for power to all components 120 V and 24 V If the setpoint configuration is correct disconnect the sensor and check its resistance Replace the sensor if its resistance value does not match the temperature in the accom...

Отзывы: