background image

PI-PR-560400 0412 (Basic Digital Setpoint Control II)

1 of 4

Viega... The global leader in plumbing, heating and pipe joining systems

301 N. Main, 9th Floor • Wichita, KS 67202 • Ph: 800-976-9819 • Fax: 316-425-7618 • www.viega.com

©2012, ProPress

®

, FostaPEX

®

, GeoFusion

®

, Seapress

®

 MegaPress

®

, MegaPressG

®

, and Viega

®

 are registered trademarks of Viega GmbH & Co. PureFlow

®

, Smart Connect

®

, Climate Panel

®

, Climate Mat

®

, Climate 

Trak

®

, MANABLOC

®

, Radiant Wizard

®

, S-no-Ice

®

, Snap Panel

®

, XL

®

 and XL-C

®

 are registered trademarks of Viega LLC.  MiniBloc

, Rapid Grid

, ProRadiant

, PolyAlloy

, SmartLoop

 and Zero Lead

 are trademarks 

of Viega LLC; ProPressG

 and ViegaPEX

 are trademarks of Viega GmbH & Co. KG.  RIDGID

®

 is a registered trademark of RIDGID, Inc.

Product

Instructions

Applications

The Viega Basic Digital Setpoint Control II is a  
general purpose temperature control with a wide  
range of applications in the HVAC industry. This  
control provides two isolated SPDT relay contacts.
The two relays are controlled by a watertight sensor,  
included with the Basic Digital Setpoint Control.  
This control is commonly used as basic heating  
and/ or cooling system control for commercial 
and residential slab applications.  

Features

• Setpoint Control for Heating and Cooling
• Simple installation and programming
• Large digital LCD display
• Reliable, economical
• Two relay outputs with individual
  Setpoint capability
• Watertight Sensor included

Specifications

Digital Setpoint Control II (17029)
Watertight Sensor (17031)

Digital Setpoint Control II 

Input:   

24V, 120V, 240V

Output:  

2 SPDT dry contacts, 

 

 

1/2 hp @ 120 VAC

 

 

9.8 FLA, 58.8 LRA

Sensor:             6' Resistor, extendable up 100'
Setpoint:            -40 - 248°F range
Differential: 

1 - 150°F range

Accuracy: 

+/- 1°F

Environment:  -40 - 140°F, 5 - 95% rH,
  non-condensing
Power draw: 

8 VA

Dimensions: 

4.91 x 8.16 x 2.37 in.

Digital Setpoint Control II

Basic Digital Setpoint Control II

Содержание Basic Digital Setpoint Control II

Страница 1: ...e control with a wide range of applications in the HVAC industry This control provides two isolated SPDT relay contacts The two relays are controlled by a watertight sensor included with the Basic Digital Setpoint Control This control is commonly used as basic heating and or cooling system control for commercial and residential slab applications Features Setpoint Control for Heating and Cooling Si...

Страница 2: ...eating and or cooling slab The sensor should be placed midway between rows of tubing and should be placed in conduit which is cast into the slab so that replacement is possible SENSOR B SENSOR A SENSOR B 24VAC SUPPLY 120V 240V SUPPLY RELAY 1 RELAY 2 Digital Input LOAD 2 LOAD 1 Wiring Sensor A is triggering the two relays Relay 1 being boiler circulator pump and Relay 2 being system circulator pump...

Страница 3: ...djusted press the right arrow button to accept and to display the Relay 1 menu 6 Select Diffrntl by pressing the right arrow button 7 Using the up and down arrows adjust the differential the range is 1 150 F once selected press the right arrow to accept and return to Relay 1 menu 8 Select Sensor A or Sensor B for Relay 1 using the up and down arrows then press right arrow button to accept 9 Select...

Страница 4: ...stered trademark of RIDGID Inc Product Instructions Troubleshooting If the system is not operating correctly first check that all electrical connections have been made properly Check for power to all components 120 V and 24 V If the setpoint configuration is correct disconnect the sensor and check its resistance Replace the sensor if its resistance value does not match the temperature in the accom...

Отзывы: