PI-PR-560400 0412 (Basic Digital Setpoint Control II)
3 of 4
Viega... The global leader in plumbing, heating and pipe joining systems
301 N. Main, 9th Floor • Wichita, KS 67202 • Ph: 800-976-9819 • Fax: 316-425-7618 • www.viega.com
©2012, ProPress
®
, FostaPEX
®
, GeoFusion
®
, Seapress
®
MegaPress
®
, MegaPressG
®
, and Viega
®
are registered trademarks of Viega GmbH & Co. PureFlow
®
, Smart Connect
®
, Climate Panel
®
, Climate Mat
®
, Climate
Trak
®
, MANABLOC
®
, Radiant Wizard
®
, S-no-Ice
®
, Snap Panel
®
, XL
®
and XL-C
®
are registered trademarks of Viega LLC. MiniBloc
™
, Rapid Grid
™
, ProRadiant
™
, PolyAlloy
™
, SmartLoop
™
and Zero Lead
™
are trademarks
of Viega LLC; ProPressG
™
and ViegaPEX
™
are trademarks of Viega GmbH & Co. KG. RIDGID
®
is a registered trademark of RIDGID, Inc.
Product
Instructions
Programming
Once the control is powered on press "MENU" button on
the control keypad to adjust settings:
At any point during the programming you may press the
"HOME" button to return back to the sensor viewing.
1. Press "MENU", then press the right arrow button when
the "Program Screen" appears
2. When the "Relay Screen" appears, press right arrow
to select Relay 1
3. Scroll up or down to select "Setpoint 1" then press the
right arrow button
4. Using the up and down arrows to adjust the Setpoint 1
desired setpoint -40 - 248 °F (this is the maximum slab
temperature setting of the heating and or cooling system)
5. Once the setpoint has been adjusted press the right
arrow button to accept and to display the "Relay 1" menu
6. Select "Diffrntl" by pressing the right arrow button
7. Using the up and down arrows, adjust the differential,
the range is 1 - 150°F, once selected press the right
arrow to accept and return to "Relay 1" menu
8. Select "Sensor A or Sensor B" for "Relay 1" using the up
and down arrows, then press right arrow button to accept
9. Select "Heat / Cool" option for "Relay 1" then press
right arrow button
10. Once you have completed all of the steps either press
the "HOME" key or scroll down using the down arrow
to "EXIT" and then press the right arrow button
11. Repeat all steps to configure "Relay 2"
Once all programming is complete the configuration can
be locked to prevent any unauthorized changes.
To Lock or Unlock the keypad simply press and hold
the "MENU" and "HOME" buttons simultaneously for
five seconds.
Operation
Heating Mode
In heating mode once the slab temperature reaches
the selected setpoint temperature the relay will be de-
energized. As the slab temperature decreases below the
selected differential the relay will energize.
Example: Slab setpoint is set to 85 °F differential is set to
5, once the slab temperature is below
80 °F the relay will be energized.
Cooling Mode
In cooling mode, the differential is above the setpoint. So
as the temperature rises higher than the selected setpoint
plus the differential the relay is energized.
Example: Slab temperature is set to 66 °F with a
differential of 2. When the slab temperature reaches 68 °F
the relay will be energized.