background image

PI-PR-560400 0412 (Basic Digital Setpoint Control II)

3 of 4

Viega... The global leader in plumbing, heating and pipe joining systems

301 N. Main, 9th Floor • Wichita, KS 67202 • Ph: 800-976-9819 • Fax: 316-425-7618 • www.viega.com

©2012, ProPress

®

, FostaPEX

®

, GeoFusion

®

, Seapress

®

 MegaPress

®

, MegaPressG

®

, and Viega

®

 are registered trademarks of Viega GmbH & Co. PureFlow

®

, Smart Connect

®

, Climate Panel

®

, Climate Mat

®

, Climate 

Trak

®

, MANABLOC

®

, Radiant Wizard

®

, S-no-Ice

®

, Snap Panel

®

, XL

®

 and XL-C

®

 are registered trademarks of Viega LLC.  MiniBloc

, Rapid Grid

, ProRadiant

, PolyAlloy

, SmartLoop

 and Zero Lead

 are trademarks 

of Viega LLC; ProPressG

 and ViegaPEX

 are trademarks of Viega GmbH & Co. KG.  RIDGID

®

 is a registered trademark of RIDGID, Inc.

Product

Instructions

Programming

Once the control is powered on press "MENU" button on 
the control keypad to adjust settings:

At any point during the programming you may press the 
"HOME" button to return back to the sensor viewing.

 1.  Press "MENU", then press the right arrow button when 

the  "Program Screen" appears

 2.  When the "Relay Screen"  appears, press right arrow 

to  select Relay 1  

 3.  Scroll up or down to select "Setpoint 1" then press the 

right arrow button

 
 4.  Using the up and down arrows to adjust the Setpoint 1 

desired setpoint -40 - 248 °F (this is the maximum slab 
temperature setting of the heating and or cooling system)

 
 5.  Once the setpoint has been    adjusted press the right 

arrow button  to accept and to display the "Relay 1" menu

 
 6.  Select "Diffrntl" by pressing the right arrow button
 
 7.  Using the up and down arrows, adjust the differential, 

the range is 1 - 150°F, once selected press the right 
arrow to accept and return to "Relay 1"  menu

  
8.  Select "Sensor A or Sensor B" for "Relay 1" using  the up 

and down arrows, then press right arrow button to accept

9.  Select "Heat / Cool" option for "Relay 1" then press 

right arrow button

10. Once you have completed all of the steps either press 

the "HOME" key or scroll down using the down arrow 
to "EXIT" and then press the right arrow button

11. Repeat all steps to configure "Relay 2"
 

Once all programming is complete the configuration can 
be locked to prevent any unauthorized changes. 

To Lock or Unlock the keypad simply press and hold  
the "MENU" and "HOME" buttons simultaneously for  
five seconds.

Operation

Heating Mode

In heating mode once the slab temperature reaches 
the selected setpoint temperature the relay will be de-
energized.  As the slab temperature decreases below the 
selected differential the relay will energize. 

Example: Slab setpoint is set to 85 °F differential is set to 
5, once the slab  temperature is below 
80 °F the relay will be energized.

Cooling Mode

In cooling mode, the differential is above the setpoint.  So 
as the temperature rises higher than the selected setpoint 
plus the differential the relay is energized.

Example: Slab temperature is set to  66 °F with a 
differential of 2. When the slab temperature reaches 68 °F 
the relay will be energized.

Содержание Basic Digital Setpoint Control II

Страница 1: ...e control with a wide range of applications in the HVAC industry This control provides two isolated SPDT relay contacts The two relays are controlled by a watertight sensor included with the Basic Digital Setpoint Control This control is commonly used as basic heating and or cooling system control for commercial and residential slab applications Features Setpoint Control for Heating and Cooling Si...

Страница 2: ...eating and or cooling slab The sensor should be placed midway between rows of tubing and should be placed in conduit which is cast into the slab so that replacement is possible SENSOR B SENSOR A SENSOR B 24VAC SUPPLY 120V 240V SUPPLY RELAY 1 RELAY 2 Digital Input LOAD 2 LOAD 1 Wiring Sensor A is triggering the two relays Relay 1 being boiler circulator pump and Relay 2 being system circulator pump...

Страница 3: ...djusted press the right arrow button to accept and to display the Relay 1 menu 6 Select Diffrntl by pressing the right arrow button 7 Using the up and down arrows adjust the differential the range is 1 150 F once selected press the right arrow to accept and return to Relay 1 menu 8 Select Sensor A or Sensor B for Relay 1 using the up and down arrows then press right arrow button to accept 9 Select...

Страница 4: ...stered trademark of RIDGID Inc Product Instructions Troubleshooting If the system is not operating correctly first check that all electrical connections have been made properly Check for power to all components 120 V and 24 V If the setpoint configuration is correct disconnect the sensor and check its resistance Replace the sensor if its resistance value does not match the temperature in the accom...

Отзывы: