Grundfix Plus-Control – Modell 4987.41
71
www.viega.com
Terminal strip order
Pos.
Cable
Functions
Indication on the connection strip
1
black – factory-fitted
15 volt mains connection
GND
2
red – factory-fitted
15 volt mains connection
+ 15V
3
black – factory-fitted
Battery connection
GND
4
red – factory-fitted
Battery connection
+ AKKU (battery)
5
green
Motor connection
Motor -
6
yellow
Motor connection
Motor +
7
Signalises backflow
RÜCK (backflow)
8
Signalises backflow
RÜCK (backflow)
9
Signalises fault
STÖR (fault)
10
Signalises fault
STÖR (fault)
11
brown
Pressure switch
Sensor
12
white
Pressure switch
Sensor
Terminal strip order 20 m cable
Pos.
Cable
Functions
Indication on the connection strip
5
Conductor 3
Motor connection
Motor -
6
Conductor 4
Motor connection
Motor +
11
Conductor 2
Pressure switch
Sensor
12
Conductor 1
Pressure switch
Sensor
Alarm and fault indicating contacts
The control unit is provided as standard with two potential-free outlets, through which other optional acoustic and optical alarm
devices can be connected. Both contacts work as a closing contact. In case of backflow, the alarm contact (clamping strip connec-
tion (7/8) is closed in "Back" mode. The error signal contact (clamping strip connection (9/10) closes in "Error" mode when an oper-
ating fault is reported. When allocating the contacts, you must ensure that a maximum current of 500 mA is not exceeded. In addi-
tion, only purely ohmic loads should be connected. An allocation of the potential-free outlets must only take place using a safety
low voltage and galvanic separation of the network. The use of a safety transformer in accordance with VDE 0551 or DIN/EN 60742
is permitted.
Technical data
Switching power supply
88-264VAC 50 / 60Hz
LCD
20 x 2 with lighting
RTC real time clock
carry-over 30 days
Battery
12V /1.2 Ah; integrated charge and test electronics for battery operation for up to 24 hours in the
case of power failure
Log
512 events
Potential-free relay outlet
Backflow and fault
Casing
Plastic casing 201 x 151 x 80 mm without hinge and PG screw fitting
Protection class in acc.
With VDE 0100
Control unit casing IP54; Grundfix Control IP
Battery fuse
4 A - inactive
Motor fuse
4 A - inactive
Closing time in case of
backflow
In both mains and battery operation approx. 10 seconds