Possibly, thorough cleaning of the sieve will be sufficient.
CAUTION!
Risk of burning due to hot magnetic coils! After prolonged
water exchange, the magnet coils get hot. Do not touch
them.
Shut the water off.
De-energise the flush valve.
Disconnect the plug from the control.
Remove the magnet valve (SW 30).
Replace the sieve.
Dispose of the old seal.
If necessary, replace the flow control.
Re-install the magnet valve with a new seal. Note the tightening
torque of the union nuts: max. 8 Nm.
Carry out a test flushing.
CAUTION!
Risk of burning due to hot magnetic coils! After prolonged
water exchange, the magnet coils get hot. Do not touch
them.
Remove the magnet valve (SW 30).
Unscrew the flow control.
Replace the flow control, seal and nut. Screw down the nut of the
flow control not more than hand-tight.
Re-install the magnet valve with the new seal. Note the tightening
torque of the union nuts: max. 8 Nm.
Carry out a test flushing.
„Replacing the floating switch“ on page 58.
Remove the lid, see "Replacing the floating switch".
Raise the floating switch and check the indication at the control.
Re-install the lid.
Carry out a test flushing.
Press the Reset button in the lid of the control.
Replacing the sieve
Replacing the flow control
Check or release the floating
switch
Handling
Flush valve universal
57 from 62