Above solution can be used up to 5 batteries maximum.
3.4.4 Series connection of batteries
The maximum battery in series is 2. This is because the standard maximum input voltage of the Lynx Ion BMS is 60 VDC.
Be sure that the battery state-of-charge is equal for each battery. If the batteries are new then they have an equal
state-of-charge.
Example of series connection of two batteries:
3.4.5 Connecting the BMS CAN-Bus network
To connect the BMS CAN-Bus communication network you will need:
CAT5 cable with RJ45 connectors (straight wiring);
Two termination resistors (supplied with the Lynx Ion BMS);
Procedure
1.
Connect the RJ45 cable between the BMS CAN-Bus connection of the Lynx Ion BMS (see appendix A for details) and the
first battery.
2.
Then connect it to the second battery (if there is one) with the next RJ45 cable.
3.
Repeat this until all batteries are connected.
4.
Place a termination resistor in the last connected battery.
5.
Place the other termination resistor in the other BMS CAN-Bus connection port of Lynx Ion BMS.
Always use machine manufactured full wired RJ45 patch cables.