WARNING: Never connect loads and chargers directly to the batteries. This can damage the batteries.
3.4.2 Installing Fuses
Fuses must be installed on both the battery side and load/charger side of the Lynx Ion BMS.
The total value of the fuses in the Distributor on the load/charger side (right side) may not exceed
the
maximum current of the safety contactor (an equal load ratio can be added depending on the
application). For the Lynx Ion BMS 400 this is 400 A and for the Lynx Ion BMS 1000 this is 1000 A.
On the battery side (left), the fuses are functional as short-circuit protection. It is recommended that this value is between 300 A
and 500 A on each connection depending on how many batteries are connected.
Possible fuses:
Fuse type
Voltage
MEGA Fuse 32V BF2 fuse (little fuse)
32V: Used for 24V systems
MEGA Fuse 58V BF2 fuse (little fuse)
58V: Used for 48V systems
3.4.3
Parallel connection of batteries
Be sure that the battery state-of-charge (SOC) is equal for each battery. If the batteries are new then they have an
equal state-of-charge (SOC is 30%).
Keep wire lengths exactly the same. Otherwise imbalance occurs.
Batteries can be connected to the Distributor or as a parallel battery string like in the figure below.
Example of parallel connection of batteries with the same cable lengths: