![Victron energy Lynx Ion BMS 1000A Скачать руководство пользователя страница 17](http://html.mh-extra.com/html/victron-energy/lynx-ion-bms-1000a/lynx-ion-bms-1000a_manual_1014744017.webp)
8 LED INDICATIONS
Firmware version 1.XX and higher.
Status LED state
Description
Off
System is in standby mode. Press START button to start up the system
On
Running
Blinking
Updating firmware of connected batteries
Flashing/beeping 2 times
Battery communication error (check BMS CAN-Bus cables)
Flashing/beeping 3 times
Under or overvoltage detected (check charger or load settings)
Flashing/beeping 4 times
Under or over temperature detected (check battery temperatures)
Flashing/beeping 5 times
Pre-charge time out occurred (check if pre-charge current is below 10A)
Flashing/beeping 6 times
Pre-charge fuse broken (check the pre-charge fuse)
Flashing/beeping 7 times
Battery configuration failure (check BMS CAN-Bus cables)
Flashing/beeping 8 times
N.A.
Flashing/beeping 9 times
Battery firmware updating failure (contact manufacturer)
Flashing/beeping 10 times
Main safety contactor failure (contact manufacturer)
Flashing/beeping 11 times
Internal measurement failure (contact manufacturer)
Flashing/beeping 12 times
System instability problem detected (contact manufacturer)
Flashing/beeping 13 times
No appropriate firmware found for connected battery (contact manufacturer)
9 MAINTENANCE
This product does not require specific maintenance. It will suffice to check all connections once a year. Avoid moisture and
oil/soot/vapors, and keep the device clean.