![Victron energy Lynx Ion BMS 1000A Скачать руководство пользователя страница 15](http://html.mh-extra.com/html/victron-energy/lynx-ion-bms-1000a/lynx-ion-bms-1000a_manual_1014744015.webp)
d.
Set action to:
Disable charger when battery is full.
(NOT force to float).
5
Go to the
charger
tab and change the settings to the following:
Set the
absorption voltage
and
float voltage
to the value’s specified in the table of chapter 6.
6 CHARGER SETTINGS
In the table below are the voltage settings specified for different type of batteries.
Battery type
System
Voltage
Absorption
voltage
Float voltage
Lithium-Ion HE Battery
48V
56,7V
55,0V
24V
28,4V
27,5V
Lithium-Ion LFP Battery Module
48V
55,2V
53,2V
24V
27,6V
26,6V