13
EN
NL
F
R
DE
ES
A
p
p
e
n
d
ix
5. CONFIGURATION – inverter/charger
5.1 Standard settings: ready for use
On delivery, the MultiPlus is set to standard factory values. In general, these settings are
suitable for single-unit operation.
Warning: Possibly, the standard battery charging voltage is not suitable for your
batteries! Refer to the manufacturer's documentation, or to your battery supplier!
Standard MultiPlus factory settings
Inverter frequency
50 Hz
Input frequency range
45 - 65 Hz
Input voltage range
180 - 265 VAC
Inverter voltage
230 VAC
Stand-alone / parallel / 3-phase
stand-alone
Search mode
off
Ground relay
on
Charger on/off
on
Battery charge curve
four-stage adaptive with BatterySafe mode
Charge current
75% of the maximum charge current
Victron Gel Deep Discharge (also suitable
for Victron AGM Deep Discharge)
Automatic equalisation charging
off
Absorption voltage
14,4 / 28,8V
Absorption time
up to 8 hours (depending on bulk time)
Float voltage
13,8 / 27,6V
Storage voltage
13,2 / 26,4V (not adjustable)
Repeated absorption time
1 hour
Absorption repeat interval
7 days
Bulk protection
on
AC input current limit
12A (= adjustable current limit for PowerControl and
PowerAssist functions)
UPS feature
on
Dynamic current limiter
off
WeakAC
off
BoostFactor
2
PowerAssist
on
Programmable relay
alarm function
Settings may only be changed by a qualified engineer
Carefully read the instructions before changes are made.
Batteries should be placed in a dry and well-ventilated area during charging.
Содержание EasySolar 12 1600
Страница 2: ......
Страница 32: ...30 ...
Страница 62: ......
Страница 92: ......
Страница 122: ......
Страница 153: ...31 EN NL FR DE ES Appendix ...
Страница 154: ......
Страница 155: ...EN NL FR DE ES Appendix www victronenergy com Appendix A overview connections ...
Страница 156: ...Appendix B installation information ...
Страница 157: ...EN NL FR DE ES Appendix www victronenergy com Appendix C Inverter PCB connections ...
Страница 158: ...Appendix D DIP switches ...
Страница 159: ......