Manual Skylla with universal input
21
When dip switch 2 “Watch” is positioned on the right, it is checked upon startup
whether the battery voltage is sufficiently high to enable a start in the float mode. If it is
not, the charger is started in the boost mode as yet.
4.10 Connecting the output voltage alarm
The charger is equipped with a potential free alarm contact (change over type).
If the battery voltage is in between Vmin and Vmax the contact is activated.
(See figure 8, remote connections: NO, NC, COM).
Model
Vmin
Vmax
24V
23,8 Vdc
33,5 Vdc
4.11 Connecting remote panels
Victron Energy provides four optional remote panels that can be connected to the
charger. See illustration 8 for the circuit board connector where the remote panels have
to be connected to.
The COV panel:
The maximum charging current of 30A, 50A or 100A, according to the model, can be
limited with an external panel. This panel, the Victron Energy COV panel, contains an
adjustable potentiometer. Limiting the maximum charging current can be useful to
meet the batteries specifications, or to make sure the shore fuse does not blow.
To connect the panel:
Disconnect the mains.
Connect the panel to the “+ pot” and “-pot” connector.
The CMV panel:
This panel indicates the charging mode and possible failures.
To connect the panel:
Disconnect the mains.
Connect the boost led to the “ L_BO” connector.
Connect the equalize led to the “L_EQ” connector.
Connect the float led to the “L_FL” connector.
Connect the failure led to the “L_FA” connector.
Connect the ground of the panel to the “GND” connector.
The CSV panel:
With the CSV panel the charger can be switched on or off. On the panel a green “on” led
is present. To operate the CSV panel you first have to switch the charger on with the
on/off switch located on the front panel of the charger.