background image

User Manual for RIS Refrigerators 

Victory

Rev. 10/20

Victory

22

HELP

Trouble Diagnosis for the User
Malfunction

Possible Cause

Likely Solution

No cooling - unit is silent

Unit not plugged in.
Fuse or circuit breaker tripped. 
Power cord plug loose in outlet.

Connect to proper voltage circuit Replace 
fuse or reset breaker.
Check outlet for loose connection, replace 
as needed

Unit cools but seems to be on all the time

Dirty condenser

Clean condenser

Space temperature too high

Dirty condenser
Evaporator iced over Unit in high 
temperature environment

Clean condenser Defrost evaporator
Reduce temperature of room

Space temperature too low

Temperature control   

Adjust or replace control

Trouble Diagnosis for the Technician
No cooling - compressor does not hum

Temp control stuck in open position

Replace temp control.

No cooling - compressor hums but does not 
start

Low voltage to unit.
Compressor starting  system failure

Check voltage, correct as needed. Check 
start relay and start capacitor. See next 
step.

No cooling - compressor starts but shuts 
off

Compressor start relay failure Compressor 
start capacitor failure

Replace relay. Replace capacitor.

No cooling - compressor cycles on and off

Overheating weak overload

Clean condenser, check fan motor and 
blade. Check refrigerant charge. Replace 
overload.

Unit cools, but is slow to pull cabinet 
temperature down

Evaporator fan not turning

Check fan(s), on multiple fan units one fan 
may be turning slowly and will need to be 
replaced.

Unit cools but turns on and off frequently

No product in cabinet. Temperature control 
defective Refrigeration issue

Fill cabinet Replace control
Have system checked

Makes excessive noise    

Tubing rattle Loose parts
Bent or broken fan blade Noisy fan motor

Check tubing for routing Check for loose 
components Replace fan blade
Replace fan motor

Содержание RIS-1D-S1-PT-HC

Страница 1: ...STRUCTIONS for all Hydrocarbon RIS Refrigerator Models 3779 CHAMPION BLVD WINSTON SALEM NC 27105 Phone 888 845 9800 Fax 800 253 5168 Web victoryrefrigeration com 809 192A Rev B 10 29 2020 SEE BACK COV...

Страница 2: ...it or void the warranty Victory reserves the right to change specifications and product design without notice Such revisions do not entitle the buyer to corresponding changes improvements additions or...

Страница 3: ...gers There may be pinch points near the door hinges Maintenance Do NOT Clean a frozen evaporator with a sharp object Clean a dirty condenser with a sharp object Store gasoline kerosene or any other fl...

Страница 4: ...necessary to move the Refrigerator after removal from the skid remove all doors and carefully push the unit at a point of no more than 36 from the bottom to avoid damage CAUTION SAFETY Push ONLY below...

Страница 5: ...substitutions will void the warranty Limitations The machine is designed for use indoors in a controlled environment It must be kept dry not overheated or subjected to excessive cold May only be conn...

Страница 6: ...36 5 8 x 90 Full Solid 8 5 R 290 130 4 59 RIS A 2D S1 PT XH HC 38 3 4 x 40 x 90 Full Solid 8 5 R 290 130 4 59 RIS A 3D S1 HC 101 1 4 x 36 3 8 x 84 3 8 3 Full Solid 10 8 R 290 150 5 29 RIS A 3D S1 PT...

Страница 7: ...t side 0 0 in at the right side Floor Load The floor on which the Refrigerator is located must be even and level free from vibrations and strong enough to support the combined weights of the unit and...

Страница 8: ...on and discard 3 Move unit as close to final position as possible before removing the skid Do NOT tip unit on its front or sides If tipped onto the back unit must not be started for 3 hours Note addit...

Страница 9: ...ention bar facing up Be careful not to dislodge clips during installation 6 Place shelves so that the retaining tab on the clip captures the shelf as shown 7 Confirm that the shelf is resting on ALL 4...

Страница 10: ...plug If the power cord becomes damaged it must be replaced with the identical cord Follow All National and Local Codes This unit must be grounded Do not use extension cords and do not disable or by p...

Страница 11: ...he system to lower the temperature faster When on the refrigeration system is always operating at maximum The temperature was set at the factory at 38 F but you can adjust it to your own selected temp...

Страница 12: ...pressor is not running The Condenser Fan is wired directly to the Compressor not through the controller EVAPORATOR FAN The Evaporator Fan runs continuously When the unit is plugged in and the evaporat...

Страница 13: ...On Defrost active Blinking Activated manually or from Digital input OFF Otherwise 3 Fans Permanently On Fans active OFF Otherwise 4 Reduced SET Economy Permanently On Energy saving active Blinking Re...

Страница 14: ...16 17 LIGHT STANDBY UP DOWN ESC SET Enter Press and Hold Press and Hold Press and Release Press and Release Press and Release Press and Release Long press 5 sec Toggles light on and off If LED is on l...

Страница 15: ...ey pad will beep when unlocked and normal key pad operations performed Setting the Operating Set Point To change the operating set point press and release the set button to enter the machine menu set...

Страница 16: ...ss the set button to display the value and use the up or down button to change the value Once the value has been selected use the escape button to confirm the new value and return the pervious menu le...

Страница 17: ...User Manual for RIS Refrigerators Victory Rev 10 20 Victory 17...

Страница 18: ...P1 Att Afd HA1 PAO dAO OAO tA1 AH2 HIGH temperature 2 alarm ON Active Automatic SP2 Att Afd HA2 PAO dAO OAO tA2 AL2 LOW temperature 2 alarm ON Active Automatic SP2 Att Afd HA2 PAO dAO OAO tA2 EA Exter...

Страница 19: ...Rinse with clean water 3 Dry with a soft cloth 4 Polish with a soft cloth wiping with the grain 5 Wipe weekly with stainless steel cleaner Weekly Interior Cleaning 1 Remove all food food related item...

Страница 20: ...ip and secure into the notch in the front right corner of the raised panel 5 Examine condenser surface if dusty brush and vacuum the dust and lint from the surface of the coil Brush up and down to avo...

Страница 21: ...amount of cleaner Heat tint or discoloration Penny Brite or Copper Brite Past NuSteel DuBois Temp or Tarnite Revere Stainless Steel Cleaner Allen Polish Steel Bright Tenacious Deposits Rusty Discolora...

Страница 22: ...ontrol No cooling compressor hums but does not start Low voltage to unit Compressor starting system failure Check voltage correct as needed Check start relay and start capacitor See next step No cooli...

Страница 23: ...ng MUST be in an area free from flame or spark It must be near an opened window or door A sign noting service of a system containing propane must be attached to the unit during refrigeration service A...

Страница 24: ...OT ALL MODELS 115VAC 60 HZ EVAP FAN BLU FAN RELAY 4 5 WHT CONTROL CIRCUIT 1 3 COMP RELAY 10 11 BRN WHT WHT BLK BLK WHT FASCIA HEATERS RED LIGHT RELAY 13 14 RED CABINET LIGHTS POWER SUPPLY BLACK WHITE...

Страница 25: ...in the Owner s Manual adjustment of door mechanisms or freight damage are not covered by this warranty For the purpose of this warranty the original purchaser shall be deemed to mean the individual or...

Страница 26: ...N LIEU OF ALL OTHER WARRANTIES EXPRESS IMPLIED OR STATUTORY INCLUDING THE IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE WHICH ARE HEREBY DISCLAIMED AND ALL OTHER OBLIGATIO...

Страница 27: ...___________ Date Of Installation _________________ Cabinet Serial Number _____________________________________________ Location Of Product Business Name _______________________________________________...

Отзывы: