23
I-800
Solvent Cementing Procedures
• Before assembling any Victaulic FireLock CPVC Sprinkler System Prod-
ucts, verify the expiration date located on the Style #899 FireLock CPVC
One-Step Solvent Cement container. Solvent cement can be used for a
period of 2 years from the date stamped on the container. DO NOT use
solvent cement that exceeds 2 years from the date stamped on the con-
tainer. Expired solvent cement must be discarded in an environmentally
friendly fashion, in accordance with local regulations.
• When cementing pipe and fittings in extremely cold temperatures, make
sure the solvent cement has not “JELLED.” Jelled solvent cement must
be discarded in an environmentally friendly fashion, in accordance with
local regulations.
• To prolong the life of solvent cement, keep containers tightly closed
when not in use. Cover the container as much as possible during use.
• If an unopened solvent cement container is subjected to freezing tem-
peratures, the cement may become extremely thick. Place the closed
container in a room temperature area where, after a short time period,
the cement will return to a usable condition. DO NOT attempt to heat sol-
vent cement. Contact Victaulic at (800) PICK VIC or (800) 742-5842 with
any questions concerning usability.
• Make sure pipes and fittings are clean and free from any moisture and
debris before applying solvent cement.
WARNING
• Before using Victaulic Style #899 FireLock CPVC One-Step Solvent Cement, refer to
ASTM– F402, "Standard Practice for Safe Handling of Solvent Cements, Primers, and
Cleaners Used for Thermoplastic Pipe and Fittings;" the Material Safety Data Sheet
(MSDS) for the solvent cement; and the important product information contained on
the solvent cement can label.
• Victaulic Style #899 FireLock CPVC One-Step Solvent Cement is highly flammable.
Make sure all ignition sources are eliminated before use.
• Avoid breathing solvent cement vapors, and use solvent cement only in well-
ventilated areas. Explosion-proof, general mechanical ventilation or local exhaust is
recommended to maintain vapor concentrations below recommended exposure
limits. In confined or partially enclosed areas, a NIOSH-approved, organic-vapor
cartridge respirator with a full-face piece is recommended.
• Avoid frequent contact with skin. PVA coated gloves and an impervious apron are
recommended.
• Avoid contact with eyes. Splash-proof chemical goggles are recommended.
Failure to follow these instructions could result in serious personal injury.
CAUTION
• DO NOT use solvent cement that exceeds 2 years from the date stamped on the
container.
• DO NOT use solvent cement that has a "JELLED" appearance.
Jelled or expired cement will not provide the required strength for a proper joint and
can result in joint failure and/or property damage.