Heat Sources and Open Ceiling Areas:
Victaulic FireLock CPVC Sprinkler Systems must be laid out so that the
piping is not closely exposed to heat producing sources, such as light fix-
tures, ballasts, and steam lines. Pipe must not be positioned directly over
open ventilation grills. During remodeling or ceiling repair, appropriate
precautions must be implemented to properly protect the piping.
Use with Other Manufacturers’ Pipes, Fittings,
and Solvent Cements:
solvent cement products
Victaulic FireLock CPVC Sprinkler System Products are UL Listed for use
in combination with UL Listed CPVC sprinkler products manufactured by
Central (pipe and fittings), Harvel (pipe), Ipex (pipe and fittings), Tyco
Fire Products (pipe and fittings), Spears (fittings), or Thompson Plastics
(fittings).
Victaulic recommends the use of Victaulic Style #899 FireLock CPVC
One-Step Solvent Cement. However, Spears FS-5; Ipex BM-5; Tyco Fire
Products TFP-500; Thompson Plastics, Inc. TPI-50; and Central Sprinkler
CSC-500 CPVC Solvent Cements can also be used in place of Victaulic
Style #899 FireLock CPVC One-Step Solvent Cement, provided that the
assembly and curing information referenced within this manual is used.
Contact Victaulic at 1-800-PICK VIC (1-800-742-5842) for further informa-
tion on Listings and Approvals.