background image

 

2

 

 

 

Programmable BI/UI inputs overview  

 

 
Binary input #1 can be configured for the following 
functions: 
1. (None): 

No function will be associated with the 

input 

 

2. (Rem 

NSB):

 remote NSB timer clock input. The 

scheduling will now be set as per the binary input. 
It provides low cost setback operation via a dry 
contact

 

• 

Contact opened = Occupied 

• 

Contact closed = Unoccupied 

3.  (Motion NO) and (Motion NC):

 Advanced PIR 

occupancy functions using a Normally Open (NO) 
or Normally Closed (NC) remote PIR motion 
sensor. Occupancy mode is now set as per applied 
PIR function and configuration. Application 
information and examples, are available on 
document: 

APP-PIR-Guide-Exx. 

This document will 

provide the installers and system designers with 
detailed examples on applications, parameter 
configuration information, sequence of operation, 
troubleshooting and diagnostic help required for the 
proper usage of the PIR accessory covers

  

4. (Window) 

EMS:

 Forces the system to disable any 

current heating or cooling action by the thermostat. 
The mode stays the same and the current setpoints 
are the same Occupied setpoints. Only the outputs 
are disabled. There is a Door/Window alarm 
displayed on the thermostat to indicate to the local 
tenant that the door/window needs to be closed for 
cooling or heating to resume. Use NC contact.

 

• 

Contact opened = System disabled with local 

Window alarm 

• 

Contact closed = System enabled 

 

Binary input #2 can be configured for the following 
functions: 

1. (None): 

No function will be associated with the 

input 

 

2. 

 (Door Dry) Door contact & Motion detector:

 

This configuration is only functional if binary input 
#1 is set to 

Motion NO 

or 

Motion NC 

or a 

PIR 

accessory cover

 is used. 

With this sequence enabled, the occupancy is now 
dictated through those 2 inputs. Any motion 
detected will set the zone to occupied status. The 
zone will remain permanently in occupied mode 
until the door contact switch opens momentarily. 
The thermostat will then go in stand-by mode. If 
more movements are detected, the occupied mode 
will resume. While the door is opened, any 
movements detected by the remote PIR sensor or 
the PIR accessory cover will be ignored. Use a 
Normally Closed contact switching device. 

• 

Contact opened = Door opened 

• 

Contact closed = Door closed 

3. 

(RemOVR):

 temporary occupancy remote override 

contact. This function disables the central button 
override function on the thermostat. The override 
function is now controlled by a manual remote 
momentarily closed contact. When configured in 
this mode, the input operates in a toggle mode. 
It is now possible to toggle between unoccupied & 
occupied setpoints for the amount of time set by 
parameter (TOccTime) temporary occupancy time. 
 

4.  

(Filter): 

a backlit flashing 

Filter 

alarm will be 

displayed on the thermostat LCD screen when the 
input is energized. It can be tied to a differential 
pressure switch that monitor filters

  

• 

Contact opened = No alarm 

• 

Contact closed = Alarm displayed 

 

5. 

(Service): 

a backlit flashing Service alarm will be 

displayed on the thermostat LCD screen when the 
input is energized. It can be tied in to the AC unit 
control card, which provides an alarm in case of 
malfunction. 

• 

Contact opened = No alarm 

• 

Contact closed = Alarm displayed 

 

Universal input #3 can be configured for the 
following functions: 
1. (None): 

No function will be associated with the 

input

 

2.  (COC/NH) Change over dry contact. Normally 

Heat: 

Used for hot

 

/

 

cold water change over 

switching in 2 pipe systems. 

 

• 

Contact closed = Cold water present 

• 

Contact opened = Hot water present 

Only used and valid if system is setup as 2 pipes. 
Parameter ( Pipe No ) set as 2 pipes. 

 

3.   (COC/NC) Change over dry contact. Normally 

Cool: 

Used for hot

 

/

 

cold water or air change over 

switching in 2 pipe systems. 

 

• 

Contact closed = Hot water present 

• 

Contact opened = Cold water present 

Only used and valid if system is setup as 2 pipes. 
Parameter ( Pipe No ) set as 2 pipes. 

 

4.   (COS) Change over analog sensor: 

Used for hot

 

/

 

cold water or air change over switching in 2 pipe 

systems.

 

Only used and valid if system is setup as 2 pipes. 
Parameter ( Pipe No ) set as 2 pipes. 

• 

If temperature is > 77 °F = Hot water present 

• 

If temperature is < 75 °F = Cold water present 

 

5.   (SS) Supply air sensor monitoring: 

Used for 

supply air temperature monitoring.

 

Only used for network reporting of the supply air 
temperature. Has no internal function in the 
thermostat. 
.

Содержание VT7300A5000

Страница 1: ...ls VT73xxX5000B is available on document ITG VT7300 PIR BAC Exx Information on the Wireless models VT73xxX5000W is available on documents ITG VWG 40 BAC Exx and LIT VWG 40 SETUP Exx Models available V...

Страница 2: ...ements detected by the remote PIR sensor or the PIR accessory cover will be ignored Use a Normally Closed contact switching device Contact opened Door opened Contact closed Door closed 3 RemOVR tempor...

Страница 3: ...ntil the tabs lock it 10 Strip each wire 1 4 inch 11 Insert each wire according to wiring diagram 13 Gently push back into hole excess wring Fig 5 14 Re Install wiring terminals in correct location Fi...

Страница 4: ...ose Heat BO 4 9 AO 2 Heat AO 2 10 BO 1 Open Cool BO 1 10 AO 1 Cool AO 1 11 BO 2 Close Cool BO 2 BO 2 Not used Blank Blank 12 BI 1 BI 1 BI 1 12 BI 1 BI 1 13 RS RS RS 13 RS RS 14 Scom Scom Scom 14 Scom...

Страница 5: ...4 Vac Com 24 Vac Com 24 Vac Com 24 V Hot 24 V Com BO3 BO2 Heating Cooling valve 24 Vac Com OR 24 V Hot 24 V Com BO1 if N O BO2 if N C 24 V Hot 24 V Com BO3 if N O BO4 if N C BO1 if N O BO2 if N C 24 V...

Страница 6: ...ing and or heating VT7300F5x00 x VT7305F5x00 x Analog actuator Mandatory Pipe no 2 pipes Fan Menu 0 L M H RA DA as per actuator If cooling only set SeqOpera 0 Cooling only If heating only set SeqOpera...

Страница 7: ...me as per actuator SeqOpera 2 Cool Reheat UI3 COS 24 V Com 24 V Hot BO2 Close Fan L Fan M Fan H High Med Low 24 Vac fan relays Cooling Heating BO4 Close Normally Closed On Off Valve Cooling and Heatin...

Страница 8: ...RS Scom RS C DI Aux Scom Scom RS Scom RS RS Wiring examples of 3 remote room sensors for averaging applications Temperature vs resistance chart for 10 Kohm NTC thermistor R25 C 10K 3 B25 85 C 3975K 1...

Страница 9: ...f humidity display is not enabled Sys mode off Override RH display is conditional to Humidity display is model and configuration dependent Model with RH sensor built in Display function can be enabled...

Страница 10: ...d menu selected Pressing repetitively the button will toggle between all the available modes Available menus are dependent on selected sequence of operation and menu selected for Fan C F Override Midd...

Страница 11: ...wireless network adapter is present If the thermostat is installed as a stand alone unit or with an Echelon adapter this parameter will not be used or displayed For BACnet MS TP models valid range to...

Страница 12: ...ut no 2 configuration Default value None None No function will be associated with the input Door Dry Door contact Motion detector This configuration is only functional if binary input 1 is set to Moti...

Страница 13: ...given of mode schedule and outdoor temperature On Scroll active Off Scroll not active AutoMode Enables Auto menu for Mode button Default value Off Enables Auto function for the mode button For sequen...

Страница 14: ...idification based on central network requirements from the BAS front end On Dehumidification Authorized Off Dehumidification Not Authorized RH set Dehumidification setpoint Default is 50 RH Used only...

Страница 15: ...y They will remain effective for the duration specified by ToccTime Setpoints will revert back to their default value after internal timer ToccTime expires To change setpoints permanently revert to No...

Страница 16: ...models VT73xxC5x00 x only Default value 1 5 minutes Floating actuator timing Maximum stroke time of floating valve actuator Range is 0 5 to 9 0 minutes in 0 5 minutes increment cph On Off devices cyc...

Страница 17: ...ions 4 94 x 3 38 x 1 13 Approximate shipping weight 0 75 lb 0 34 kg Agency Approvals all models UL UL 873 US and CSA C22 2 No 24 Canada File E27734 with CCN XAPX US and XAPX7 Canada Industry Canada IC...

Отзывы: