16

 

aux cont 

Auxiliary contact function & 
configuration 

 

Default value = 

Not Used 

0 Aux contact function used for reheat 
IF SEQUENCE IS SET TO REHEAT THROUGH NETWORK OR LOCAL

, Ignore 

this parameter 
 

The output will directly follow the occupancy of the thermostat 
1

 

Auxiliary NO

, Occ or St-By = Contact Closed / Unoccupied = Contact Opened 

2

 

Auxiliary NC

, Occ or St-By = Contact Opened / Unoccupied = Contact Closed 

 

Output to follow directly main occupancy and Fan on command 

Typically used for 2 position fresh air damper applications. 

3

 

Auxiliary NO

, Occ or St-By & Fan On = Contact Closed / Unoccupied & Fan On 

or Off = Contact Opened 

4

 

Auxiliary NC

, Occ or St-By & Fan On = Contact Opened / Unoccupied & Fan 

On or Off = Contact Closed

  

 
Output to follow secondary network occupancy command

 

5

 

Auxiliary On/Off Control

 through auxiliary network command. The output can 

be commanded through the network for any required auxiliary functions through a 
separate & dedicated network variable. 

FL time

 

For floating models 

VT73xxC5x00(x) 

only 

Default value: 

1.5 minutes

 

Floating actuator timing 
Maximum stroke time of floating valve actuator. 
 
Range is: 

0.5 to 9.0

 

minutes

 in 0.5 minutes increment 

cph

 

On/Off devices cycles per hour 
For On/Off models & sequences  

VT73xxC5x00(x) 

only 

Default value = 

4 C.P.H. 

 

Will set the maximum number cycles per hour under normal control operation.  It 
represents the maximum number of cycles that the equipment will turn ON and 
OFF in one hour. 
Note that a higher C.P.H will represent a higher accuracy of control at the expense 
of wearing mechanical components faster. 
Range is: 

3, 4, 5, 6,7 & 8 C.P.H. 

RA/DA

 

For Analog models 

VT73xxF5x00(x) 

only 

Default value: 

DA signal

 

Reverse acting or Direct acting signal for Analog output signals 

DA 

= Direct acting, 0 to 100 % = 0 to 10 Vdc 

RA

 = Reverse acting, 0 to 100 % = 10 to 0 Vdc 

Reheat

 

Default value: 

0 = 15 minute

 

Sets the reheat output time base 
Valid only if reheat sequences are enabled 

0 = 

15 minutes

 

1 = 

10 seconds for Solid state relays 

UI3 dis 

Display UI3 value.  

Used as diagnostic / service help to troubleshoot and diagnose sensor operation 
Supply or change over temperature when UI3 is configured as an analog input  
( SS or COS ) 

Содержание VT7300A5000

Страница 1: ...ls VT73xxX5000B is available on document ITG VT7300 PIR BAC Exx Information on the Wireless models VT73xxX5000W is available on documents ITG VWG 40 BAC Exx and LIT VWG 40 SETUP Exx Models available V...

Страница 2: ...ements detected by the remote PIR sensor or the PIR accessory cover will be ignored Use a Normally Closed contact switching device Contact opened Door opened Contact closed Door closed 3 RemOVR tempor...

Страница 3: ...ntil the tabs lock it 10 Strip each wire 1 4 inch 11 Insert each wire according to wiring diagram 13 Gently push back into hole excess wring Fig 5 14 Re Install wiring terminals in correct location Fi...

Страница 4: ...ose Heat BO 4 9 AO 2 Heat AO 2 10 BO 1 Open Cool BO 1 10 AO 1 Cool AO 1 11 BO 2 Close Cool BO 2 BO 2 Not used Blank Blank 12 BI 1 BI 1 BI 1 12 BI 1 BI 1 13 RS RS RS 13 RS RS 14 Scom Scom Scom 14 Scom...

Страница 5: ...4 Vac Com 24 Vac Com 24 Vac Com 24 V Hot 24 V Com BO3 BO2 Heating Cooling valve 24 Vac Com OR 24 V Hot 24 V Com BO1 if N O BO2 if N C 24 V Hot 24 V Com BO3 if N O BO4 if N C BO1 if N O BO2 if N C 24 V...

Страница 6: ...ing and or heating VT7300F5x00 x VT7305F5x00 x Analog actuator Mandatory Pipe no 2 pipes Fan Menu 0 L M H RA DA as per actuator If cooling only set SeqOpera 0 Cooling only If heating only set SeqOpera...

Страница 7: ...me as per actuator SeqOpera 2 Cool Reheat UI3 COS 24 V Com 24 V Hot BO2 Close Fan L Fan M Fan H High Med Low 24 Vac fan relays Cooling Heating BO4 Close Normally Closed On Off Valve Cooling and Heatin...

Страница 8: ...RS Scom RS C DI Aux Scom Scom RS Scom RS RS Wiring examples of 3 remote room sensors for averaging applications Temperature vs resistance chart for 10 Kohm NTC thermistor R25 C 10K 3 B25 85 C 3975K 1...

Страница 9: ...f humidity display is not enabled Sys mode off Override RH display is conditional to Humidity display is model and configuration dependent Model with RH sensor built in Display function can be enabled...

Страница 10: ...d menu selected Pressing repetitively the button will toggle between all the available modes Available menus are dependent on selected sequence of operation and menu selected for Fan C F Override Midd...

Страница 11: ...wireless network adapter is present If the thermostat is installed as a stand alone unit or with an Echelon adapter this parameter will not be used or displayed For BACnet MS TP models valid range to...

Страница 12: ...ut no 2 configuration Default value None None No function will be associated with the input Door Dry Door contact Motion detector This configuration is only functional if binary input 1 is set to Moti...

Страница 13: ...given of mode schedule and outdoor temperature On Scroll active Off Scroll not active AutoMode Enables Auto menu for Mode button Default value Off Enables Auto function for the mode button For sequen...

Страница 14: ...idification based on central network requirements from the BAS front end On Dehumidification Authorized Off Dehumidification Not Authorized RH set Dehumidification setpoint Default is 50 RH Used only...

Страница 15: ...y They will remain effective for the duration specified by ToccTime Setpoints will revert back to their default value after internal timer ToccTime expires To change setpoints permanently revert to No...

Страница 16: ...models VT73xxC5x00 x only Default value 1 5 minutes Floating actuator timing Maximum stroke time of floating valve actuator Range is 0 5 to 9 0 minutes in 0 5 minutes increment cph On Off devices cyc...

Страница 17: ...ions 4 94 x 3 38 x 1 13 Approximate shipping weight 0 75 lb 0 34 kg Agency Approvals all models UL UL 873 US and CSA C22 2 No 24 Canada File E27734 with CCN XAPX US and XAPX7 Canada Industry Canada IC...

Отзывы: