H.264 16-Channel Encoder Installation and Configuration Guide
|
11
To connect an alarm input to the H264-16CH-ENCDR:
1. Locate the alarm cable(s) near the encoder. These wires (pairs) will
be connected to the alarm inputs terminal block connections (refer to
Figure below). There are eight alarms available.
2. Connect one alarm wire to the alarm connection on the terminal
block. The second wire is connected to GND.
3. Connect the terminal block connector to the alarm connectors on the
rear panel.
4. Connect the other end of this cable to the appropriate alarm output
(N.O. or N.C. dry contact).
Note:
Upon power-up, the state of the alarm inputs is sampled and stored as the
default, non-alarmed state. Therefore, ensure that all the alarm sensors are
in a non-alarmed state prior to power-up.
Note:
Users may select N.O. and N.C. according to the sensor type being installed.
To connect a relay (alarm output) to the H264-16CH-ENCDR:
1. Locate the relay cable(s) near the encoder. These cable wires (pairs)
will be connected to the Relays and GND (Ground) terminal block.
There are eight relays available.
2. Connect positive (+) terminal of customer-supplied relay coil to the
positive (+) terminal of separate external power supply (customer-
supplied).